Skip to content
Schneider Electric

Schneider Electric TeSys Deca LRD32 Thermal Overload Relay, 23–32A, Class 10A

0 Reviews
SKU
LRD32

The Schneider Electric TeSys Deca LRD32 is a differential thermal overload relay for three-phase motor protection. Its setting adjusts from 23–32 A, and it is Class 10A per IEC 60947-4-1. It has one normally open and one normally closed auxiliary contact and is listed as compatible with LC1D25, LC1D32, and LC1D38 contactors.

  • Adjustable 23–32 A range
  • Class 10A trip class
  • Three-phase motor protection
  • LC1D contactor compatibility
  • 1 NO + 1 NC auxiliary contacts
  • 690 V AC operational rating

The Schneider Electric TeSys Deca LRD32 is a differential thermal overload relay for three-phase motor protection. Its setting adjusts from 23–32 A, and it is Class 10A per IEC 60947-4-1. It has one normally open and one normally closed auxiliary contact and is listed as compatible with LC1D25, LC1D32, and LC1D38 contactors.

Product Overview

The Schneider Electric TeSys Deca LRD32 is a differential thermal overload relay for three-phase motor protection. Its setting adjusts from 23–32 A, and it is Class 10A per IEC 60947-4-1. It has one normally open and one normally closed auxiliary contact and is listed as compatible with LC1D25, LC1D32, and LC1D38 contactors.

  • Adjustable 23–32 A range
  • Class 10A trip class
  • Three-phase motor protection
  • LC1D contactor compatibility
  • 1 NO + 1 NC auxiliary contacts
  • 690 V AC operational rating

Technical Specifications

Product information and specifications for the selected item.

SKU: LRD32

Product Information

BrandSchneider Electric
MPNLRD32
SKULRD32
CategoryDisconnects & Safety Switches

Key Specs

Maximum Amperage (A)32
Phase Type3 Phase

Switch Ratings

Maximum Amperage (A)32
Phase Type3 Phase
Network frequency0...400 Hz
Rated insulation voltagePower circuit: 600 (CSA); 600 (UL); 690 (IEC 60947-4-1) V
Tripping threshold1.14 +/- 0.06 Ir
Conventional free-air thermal current (signalling circuit)5 A
Network typeAC; DC
Dielectric strength1.89 kV at 50 Hz, IEC 60947-1
Permissible signalling-circuit currents1.5 at 240 V AC-15; 0.1 at 250 V DC-13
Rated operational voltage690 V AC, 0...400 Hz; power circuit, IEC 60947-4-1
Phase-failure sensitivityTripping current 130% of Ir on two phases, the last one at 0
Rated impulse withstand voltage6 kV

Disconnect Configuration

Auxiliary contact composition1 NO + 1 NC
Mounting supportPlate with specific accessories; rail with specific accessories; under contactor
Product compatibilityLC1D32; LC1D25; LC1D38
Terminal tightening torqueControl circuit: 1.7; power circuit: 2.5 N·m
Control-circuit terminal connectionsScrew-clamp terminals; 2 conductors, 1…2.5 mm²; flexible with or without cable end, or solid
Power-circuit terminal connectionsScrew-clamp terminals; 1 conductor; flexible without cable end or solid: 1.5…10 mm²; flexible with cable end: 1…6 mm²
ControlsRed push-button stop; blue push-button reset
ApplicationMotor protection
Relay typeDifferential thermal overload relay

Enclosure & Certifications

Certifications and ListingsCE Certified, CSA Listed, IEC Certified, UL Listed
IP degree of protectionIP20 conforming to IEC 60529
Flame retardanceV1 conforming to UL 94
Mechanical robustnessVibrations: 6 Gn; shocks: 15 Gn for 11 ms
Ambient storage temperature-60…70 °C
Ambient operating temperature without derating-20…60 °C

Dimensions & Weight

Height (in.)2.5984
Width (in.)1.7717
Length (in.)2.7559
Weight (lb.)0.2734