Skip to content
Schneider Electric

Schneider Electric TeSys Deca Nonreversing 3-Pole IEC Contactor, 12A, 120VAC Coil

0 Reviews
SKU
LC1D12G7

The Schneider Electric TeSys Deca LC1D12G7 is a nonreversing, three-pole IEC contactor with three normally open main contacts, a 120 VAC 50/60 Hz coil, and screw-clamp terminals. It is rated 12 A for AC-3 service at up to 440 V AC.

  • Three-pole, nonreversing design
  • 12 A AC-3 rating
  • 120 VAC 50/60 Hz coil
  • 25 A tungsten and ballast ratings
  • Auxiliary 1 NO + 1 NC contacts
  • Screw-clamp terminals

The Schneider Electric TeSys Deca LC1D12G7 is a nonreversing, three-pole IEC contactor with three normally open main contacts, a 120 VAC 50/60 Hz coil, and screw-clamp terminals. It is rated 12 A for AC-3 service at up to 440 V AC.

Product Overview

The Schneider Electric TeSys Deca LC1D12G7 is a nonreversing, three-pole IEC contactor with three normally open main contacts, a 120 VAC 50/60 Hz coil, and screw-clamp terminals. It is rated 12 A for AC-3 service at up to 440 V AC.

  • Three-pole, nonreversing design
  • 12 A AC-3 rating
  • 120 VAC 50/60 Hz coil
  • 25 A tungsten and ballast ratings
  • Auxiliary 1 NO + 1 NC contacts
  • Screw-clamp terminals

Technical Specifications

Product information and specifications for the selected item.

SKU: LC1D12G7

Product Information

BrandSchneider Electric
MPNLC1D12G7
SKULC1D12G7
UPC / GTIN785901207047
CategoryLighting Contactors

Key Specs

Number of Poles3
Coil Voltage120 VAC
Contact TypeN.O.
Height (in.)3.0315

Switching & Electrical

Number of Poles3
Coil Voltage120 VAC
Contact TypeN.O.
Rated insulation voltagePower circuit: 690 V per IEC 60947-4-1; 600 V per CSA and UL.
Resistive electric-heating rating25 A at 600 V AC; 250,000 cycles under the resistive electric-heating control rating.
Insulation coordination6 kV impulse withstand; overvoltage category III; pollution degree 3.
Mounting supportRail or plate.
Auxiliary contact arrangement1 NO + 1 NC auxiliary contacts; mechanically linked, with 1 NC mirror contact.
Making and breaking capacityPower-circuit making and breaking capacity: 250 A at 440 V; signalling-circuit making capacity: 140 A AC or 250 A DC.
Associated fuse ratingsPower circuit: 40 A gG for coordination type 1 or 25 A gG for type 2 at ≤690 V; signalling circuit: 10 A gG.
Rated operational voltagePower circuit: ≤690 V AC at 25–400 Hz; ≤300 V DC.
Terminal tightening torque1.7 N·m (15.05 lbf·in) for power and control screw-clamp terminals.
Conventional free-air thermal current25 A for the power circuit and 10 A for the signalling circuit at 140 °F (60 °C).
Standards and certificationsCertifications: UL, CCC, CSA, Marine, UKCA, EAC and CB Scheme; standards include IEC/EN 60947-4-1 and 60947-5-1, and UL 60947-4-1.
CSA high-fault short-circuit ratingCSA optional high-fault rating: maximum 85 kA RMS at 480 V with a thermal-magnetic breaker rated no greater than 35 A and interrupting rating at least 100 kA RMS.
Terminal wiringScrew-clamp terminals; power-circuit flexible conductors without cable ends: 1–4 mm².
Operating time and rate12–22 ms closing; 4–19 ms opening; maximum 3,600 cycles/h at 60 °C.
Tungsten and ballast load ratingsFor LC1D12: tungsten, 25 A at 480 V AC, 3-phase wye; ballast, 25 A at 600 V AC, single-phase or 3-phase wye.
Short-circuit current rating (SCCR)Up to 100 kA.
Ambient temperature and operating altitudePermissible ambient: −40…60 °C; 60…70 °C with derating. Operating altitude: 0…3000 m.
Mechanical and electrical durability15 million mechanical cycles; electrical durability: 2 million cycles at 12 A AC-3 or AC-3e ≤440 V, and 0.8 million cycles at 25 A AC-1 ≤440 V.
Application and utilization categoriesMotor-control and resistive-load applications; AC-3, AC-3e, AC-1 and AC-4 utilization categories.
Coil technology and operating limitsNo built-in suppressor module; operational range 0.8–1.1 Uc at 50 Hz and 0.85–1.1 Uc at 60 Hz at −40…60 °C.
Rated short-time withstand currentPower circuit at 40 °C: 210 A for 1 s; 105 A for 10 s; 61 A for 1 min; 30 A for 10 min.
Rated operational current by utilization categoryAt ≤440 V AC: 25 A for AC-1; 12 A for AC-3 and AC-3e, at <140 °F (60 °C).
Degree of protectionIP20 on the front face, per IEC 60529.
Motor horsepower rating10 hp at 575/600 V AC, 50/60 Hz, for 3-phase motors.

Dimensions & Weight

Height (in.)3.0315
Width (in.)1.7717
Length (in.)3.3858
Weight (lb.)0.7165