The SensorSwitch PP20 Contractor Select power pack combines 120/277 VAC input with a 20 A normally open relay for lighting-load switching. It supplies Class II 15 VDC sensor power, supports up to 14 low-voltage sensors, and is plenum-rated.

  • 20 A General-Use Relay
  • 120/277 VAC Input
  • Class II 15 VDC Sensor Power
  • Up to 14 Low-Voltage Sensors
  • Plenum-Rated Power Pack
  • Normally Open Relay Contact

Product Overview

The SensorSwitch PP20 Contractor Select power pack combines 120/277 VAC input with a 20 A normally open relay for lighting-load switching. It supplies Class II 15 VDC sensor power, supports up to 14 low-voltage sensors, and is plenum-rated.

Technical Specifications

Product information and specifications for the selected item.

SKU: PP20

Product Information

BrandSensorSwitch
MPNPP20
SKUPP20
UPC / GTIN745975809592
CategoryLighting Contactors

Switching & Electrical

Contact TypeN.O.
Warrantied operating temperature14°F to 122°F (-10°C to 50°C); 14°F to 113°F (-10°C to 45°C) if enclosed within a junction box
Mounting arrangementElongated nipple; mounts through a 1/2-inch junction-box knockout or inside an adjacent box for local code requirements
Regulatory listingscUL, UL
Plug-load controlPP20 is shown in a plug-load control wiring arrangement
Tungsten-load rating5 A, 600 W at 120 VAC
Relay-contact protection and endurancePatented relay contact protection; tested to over 400,000 cycles at rated load
Single-sensor configurationOne sensor can control one circuit
Supply wiring requirementSingle-phase hot-and-neutral system
Sensor capacity with R-option sensors8 sensors
Relay current draw when on40 mA
Motor-load rating1 HP at 240 VAC
Low-voltage sensor capacityUp to 14 sensors
Relay-control capacityUp to 3 relays per transformer, including relay(s) inside the power pack
Sensor power output15 VDC
Multi-sensor configurationMultiple sensors can control one circuit
Line-side or switch-leg wiringMay be wired continuously hot (line side) or on the switch leg (load side) without nuisance delays at turn-on
Low-voltage wiring18–22 AWG low-voltage wire; shielding not required
Relative humidityUp to 90%, non-condensing % RH
UL listingEnergy Management Equipment, UL 916; file E167435
Line-voltage lead identification120 V uses the black lead; 277 V uses the orange lead
Transformer output capacityUp to 150 mA
General-use switched-load rating20 A
Maximum connected power packs5 packs
Sensor-side conductor colorsSensor-side wiring is shown with red, black, and white conductors