The Siemens 48504-846 is a single-position, 4-jaw ringless meter socket for underground, single-phase, 3-wire service, rated 320 A continuous and 400 A maximum. It includes a lever-operated jaw-release bypass and a factory-installed lug for connection to two enclosed circuit breakers; the enclosure is NEMA 3R, and the product is UL Listed and rated 600 V AC.

  • 320A Continuous, 400A Maximum
  • Single-Phase, 3-Wire Service
  • Single-Position, 4-Jaw Ringless Socket
  • Underground Feed, Bottom Entry Only
  • Lever-Operated Jaw-Release Bypass
  • Line Lugs: #4–600 kcmil

Product Overview

The Siemens 48504-846 is a single-position, 4-jaw ringless meter socket for underground, single-phase, 3-wire service, rated 320 A continuous and 400 A maximum. It includes a lever-operated jaw-release bypass and a factory-installed lug for connection to two enclosed circuit breakers; the enclosure is NEMA 3R, and the product is UL Listed and rated 600 V AC.

Technical Specifications

Product information and specifications for the selected item.

SKU: 48504-846

Product Information

BrandSiemens
MPN48504-846
SKU48504-846
CategoryMeter Sockets

Key Specs

Maximum Amperage (A)400
Meter Socket TypeRingless
Service feed typeUnderground only
Bypass TypeLever Bypass
Number of Spaces1

Service Ratings

Maximum Amperage (A)400
Phase Type1 Phase
Bypass capacity100 %
Load conductor range(2) #6 - 350 KCMIL
Line conductor range#4 - 600 KCMIL
Voltage rating600 V AC

Meter Configuration

Meter Socket TypeRingless
Service feed typeUnderground only
Bypass TypeLever Bypass
Number of Jaws4
Number of Spaces1
Load-connector clearancePrevent load connectors from rotating into contact with the neutral stud
Swing latch materialStainless steel
Disconnect sleeve compatibilityCannot be used
Terminal materialTin-plated copper
Clear plastic shieldThe clear plastic shield guides meter blades into the jaws and must never be removed
Meter-handling warningDo not use the bypass as a jumper; disconnect all customer load before installing or removing the meter
Hub openingBlank
Load-side connection limitNo more than two; additional connections require a separate junction box
Enclosed-breaker connection lugFactory-installed lug for wiring the socket to (2) enclosed circuit breakers
Block materialGlass reinforced polyester
Circuit-breaker lugFactory-installed lug connects the meter socket to two enclosed circuit breakers
Meter-change bypass operationRaise the bypass handle to up/open before meter installation or removal; in this position the jaws are bridged and the load side is energized
Hub provisionBlank
Service-conductor entryBottom entry only; no top entry

Package & Certifications

Certifications and ListingsUL Listed
Enclosure ratingNEMA 3R

Dimensions & Weight

Height (in.)28
Width (in.)12.8
Length (in.)5

Product Documents

Your cart

0 products 0 units

Your cart is empty.