Skip to content

Siemens 3VA62 250A 3-Pole Class M Molded Case Circuit Breaker, ETU350 LSI, Without Lugs

0 Reviews
SKU
3VA6225-5HN31-0AA0

Siemens 3VA62 is a 250 A, three-pole molded case circuit breaker rated 690 V AC, with an ETU350 LSI electronic trip unit and Class M interrupting capacity. It is supplied without lugs; the product data lists UL listing, CSA certification, and RoHS.

  • 250 A, Three-Pole Rating
  • UL 489 Short-Circuit Ratings
  • ETU350 LSI Electronic Trip
  • 690 V AC Rating
  • Supplied Without Lugs
  • 4.1 × 7.8 × 4.2 in Dimensions

Siemens 3VA62 is a 250 A, three-pole molded case circuit breaker rated 690 V AC, with an ETU350 LSI electronic trip unit and Class M interrupting capacity. It is supplied without lugs; the product data lists UL listing, CSA certification, and RoHS.

Product Overview

Siemens 3VA62 is a 250 A, three-pole molded case circuit breaker rated 690 V AC, with an ETU350 LSI electronic trip unit and Class M interrupting capacity. It is supplied without lugs; the product data lists UL listing, CSA certification, and RoHS.

  • 250 A, Three-Pole Rating
  • UL 489 Short-Circuit Ratings
  • ETU350 LSI Electronic Trip
  • 690 V AC Rating
  • Supplied Without Lugs
  • 4.1 × 7.8 × 4.2 in Dimensions

Technical Specifications

Product information and specifications for the selected item.

SKU: 3VA6225-5HN31-0AA0

Product Information

BrandSiemens
MPN3VA6225-5HN31-0AA0
SKU3VA6225-5HN31-0AA0
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)250
Voltage690 V
Interruption TypeStandard Trip
Breaker TypeStandard
Neutral Connection TypeNon-Neutral

Electrical Ratings

Maximum Amperage (A)250
Voltage690 V
Interruption TypeStandard Trip
Short-circuit pickup range (Isd)1.5–10 × Ir
Operating ambient temperature range−25 °C to 70 °C
Electrical endurance12,000 cycles at AC-1, 380/415 V; 8,400 cycles at AC-1, 690 V; 12,000 cycles at 480 V; 8,400 cycles at 600 V
Ground-fault protectionNo ground-fault monitoring; grounding protection is not provided
Storage temperature range−40 °C to 80 °C
Operational current at 60 °C232 A
UL 489 short-circuit breaking capacity100 kA at 240 V; 35 kA at 480 V; 18 kA at 600 V
Typical mechanical service life25,000 operating cycles (typical)
100%-rated breakerNo
IEC short-circuit making capacity (Icm)187 kA at 240 V; 121 kA at 415 V; 4.5 kA at 690 V
Short-time pickup setting range (Isd)1.5–10 × Ir
IEC 60947-2 service breaking capacity (Ics)85 kA at 240 V; 55 kA at 415 V; 3 kA at 690 V
Short-time trip delay maximum (tsd)Maximum setting 0.4 s
IEC 60947-2 ultimate breaking capacity (Icu)85 kA at 240 V; 55 kA at 415 V; 3 kA at 690 V
Long-time trip delay range (tr)0.5–13 s, with I2t characteristic
Long-time overload pickup range (Ir)Adjustable from 100 A to 250 A
Operational current at elevated ambient temperatures241 A at 55 °C; 232 A at 60 °C; 222 A at 65 °C; 213 A at 70 °C
Instantaneous trip current (Ii)2,500 (fixed) A
Power lossMaximum 42 W; 14 W per pole at rated current in hot AC operating state
Instantaneous trip pickup (Ii)10 × In
Overload pickup adjustment range (Ir)100–250 A
Operational current at 55 °C241 A

Breaker Configuration

Breaker TypeStandard
Neutral Connection TypeNon-Neutral
Series Type3VA62

Pack & Smart Features

Bundle/SingleSingle Product
Pack OptionsSingle Item
Integrated communication and measurement functionsNo communication function; no other measurement function

Certifications

Certifications and ListingsCSA Certified, ROHS, UL Listed
Front protection classIP40 on the front

Dimensions & Weight

Height (in.)7.795
Width (in.)4.134
Length (in.)4.213
Weight (lb.)4.861

Product Documents