Skip to content

Siemens 3VA62 Class M 100A 3P UL Molded-Case Circuit Breaker, ETU350 LSI, Without Lugs

0 Reviews
SKU
3VA6210-5HN31-0AA0

The Siemens 3VA6210-5HN31-0AA0 is a 100 A, 3-pole 3VA62 Class M UL molded-case circuit breaker on a 250 A frame, with an ETU350 LSI electronic trip unit and no lugs. Its product description gives a 690 V AC rating.

  • 100 A Current Rating
  • Three-Pole Configuration
  • 250 A Frame
  • ETU350 LSI Trip Unit
  • UL 489 Interrupting Ratings
  • Supplied Without Lugs

The Siemens 3VA6210-5HN31-0AA0 is a 100 A, 3-pole 3VA62 Class M UL molded-case circuit breaker on a 250 A frame, with an ETU350 LSI electronic trip unit and no lugs. Its product description gives a 690 V AC rating.

Product Overview

The Siemens 3VA6210-5HN31-0AA0 is a 100 A, 3-pole 3VA62 Class M UL molded-case circuit breaker on a 250 A frame, with an ETU350 LSI electronic trip unit and no lugs. Its product description gives a 690 V AC rating.

  • 100 A Current Rating
  • Three-Pole Configuration
  • 250 A Frame
  • ETU350 LSI Trip Unit
  • UL 489 Interrupting Ratings
  • Supplied Without Lugs

Technical Specifications

Product information and specifications for the selected item.

SKU: 3VA6210-5HN31-0AA0

Product Information

BrandSiemens
MPN3VA6210-5HN31-0AA0
SKU3VA6210-5HN31-0AA0
UPC / GTIN4042948857779
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)100
Voltage690 V AC
Interruption TypeStandard Trip
Breaker TypeStandard
Neutral Connection TypeNon-Neutral

Electrical Ratings

Maximum Amperage (A)100
Voltage690 V AC
Interruption TypeStandard Trip
UL 489 100%-rated breakerNo
IEC 60947 ultimate short-circuit breaking capacity (Icu)85 at 240 V; 55 at 415 V; 3 at 690 V kA
IEC 60947 short-circuit making capacity (Icm)187 at 240 V; 121 at 415 V; 4.5 at 690 V kA
Adjustable short-time pickup setting (Isd)150–1,000 A
Long-time trip delay (tr, I²t)0.5–17 s
Mechanical service life25,000 typical operating cycles
Instantaneous trip pickup setting (Ii)1,200 (fixed) A
Short-time trip delay (tsd, I²t)0.0001–0.4 s
Overload pickup setting range (Ir)40–100 A
Storage temperature range-40 to 80 °C
Maximum power loss6.7 W
IEC 60947 service short-circuit breaking capacity (Ics)85 at 240 V; 55 at 415 V; 3 at 690 V kA
Operating ambient temperature range-25 to 70 °C
Power loss per pole at rated current2.23 W
Electrical endurance12,000 at 480 V; 8,400 at 600 V cycles
Adjustable long-time pickup setting (Ir)40–100 A
Delayed short-circuit pickup setting range (Isd)1.5–10 × Ir
UL 489 short-circuit interrupting ratings240 V: 100; 480Y/277 V: 35; 480 V: 35; 600Y/347 V: 18; 600 V: 18 kA
UL 489 interrupting capacity100 at 240 V; 35 at 480 V; 18 at 600 V kA

Breaker Configuration

Breaker TypeStandard
Neutral Connection TypeNon-Neutral
Series Type3VA62
Trip-unit configurationComplete breaker with non-interchangeable trip unit
Auxiliary changeover contacts0 contacts
Reverse-feed application suitabilitySuitable for reverse-feed applications
Trip-unit adjustment methodParameters selected with a setting knob

Pack & Smart Features

Bundle/SingleSingle Product
Pack OptionsSingle Item

Certifications

Certifications and ListingsCSA Certified, ROHS, UL Listed
Front protection ratingIP40

Dimensions & Weight

Height (in.)7.8
Width (in.)4.13
Length (in.)3.39
Weight (lb.)5.51

Product Documents

Your cart

1 product 1 unit