Skip to content

Siemens GF226NRA General Duty Fusible Safety Switch, 600A, 240V, 2P, Type 3R

0 Reviews
SKU
GF226NRA

The Siemens GF226NRA is a 600 A, two-pole, 240 V fused outdoor safety switch. Specifications state that it is suitable for use as service entrance equipment, with short-circuit ratings that vary by fuse class.

  • 600 A, 2-Pole, 240 V
  • Fuse-Class AIC Ratings
  • Service Entrance Suitability
  • Line/Load Lug and Wire Ranges
  • Maximum Horsepower Ratings
  • Touch-Safe Internal Shields

The Siemens GF226NRA is a 600 A, two-pole, 240 V fused outdoor safety switch. Specifications state that it is suitable for use as service entrance equipment, with short-circuit ratings that vary by fuse class.

Product Overview

The Siemens GF226NRA is a 600 A, two-pole, 240 V fused outdoor safety switch. Specifications state that it is suitable for use as service entrance equipment, with short-circuit ratings that vary by fuse class.

  • 600 A, 2-Pole, 240 V
  • Fuse-Class AIC Ratings
  • Service Entrance Suitability
  • Line/Load Lug and Wire Ranges
  • Maximum Horsepower Ratings
  • Touch-Safe Internal Shields

Technical Specifications

Product information and specifications for the selected item.

SKU: GF226NRA

Product Information

BrandSiemens
SKUGF226NRA
CategoryDisconnects & Safety Switches

Key Specs

Maximum Amperage (A)600
Disconnect TypeSafety Switch
NEMA Enclosure RatingNEMA 3R

Switch Ratings

Maximum Amperage (A)600
Short-Circuit Rating10,000 AIC with Class H fuses; 100,000 AIC with Class R, J, and T fuses
Maximum Horsepower Ratings200 hp at 3-phase 240 V AC; 50 hp at 250 V DC

Disconnect Configuration

Disconnect TypeSafety Switch
FusedFused
Cover InterlockSingle cover interlock
Fuse Clip DesignSpring-loaded heat-sink fuse clip
Neutral Grounding FeatureExtra ground lug on neutral
Fastening MethodSurface
Terminal DesignLay-in lugs
Actuating Element DesignSingle throw
Switching ActionQuick-make and break
Equipment Ground Wire Range(2) 14–2/0 AWG
100% Neutral Wire Range(2) 1/0–600 kcmil or (2) 6–300 kcmil AWG/kcmil
Electrical ConnectionMechanical lugs
Line/Load Wire Range With NEC Bending Space(1) 1/0 AWG–600 kcmil or (2) 1/0 AWG–500 kcmil AWG/kcmil
Blade VisibilityVisible blade design
Line/Load Lug Wire Range(2) 1/0 AWG–750 kcmil AWG/kcmil
Line/Load Lug CapacityUL-approved for two wires per lug; two lugs at each line and load end per pole

Enclosure & Certifications

NEMA Enclosure RatingNEMA 3R
Certifications and ListingsCSA Listed, UL Listed
Internal Shield SafetyInternal shields meet 2020 NEC 230.62 touch-safe requirements for service entrance equipment
Enclosure MaterialGalvanized steel
Service Entrance SuitabilitySuitable for use as service entrance equipment
Enclosure Thickness0.060 (16 gauge) in
FinishANSI Grey #61 paint
Operating Ambient Temperature Range-29 to 85 °C

Dimensions & Weight

Height (in.)45.81
Width (in.)23.404
Length (in.)9.93
Tangential Knockout Conduit Sizes2.00, 2.50, 3.00, and 3.50 in
Knockout ConfigurationTangential and ground knockouts are bottom-only; ground knockout is 0.50–0.75 in diameter