Siemens P2 QR Single-Mount Branch Breaker Strap Kit, 2P/3P

0 Reviews
SKU
BBKQR1

The Siemens BBKQR1 is a single-mount branch-breaker strap kit for QR-frame 2-pole and 3-pole breakers in Siemens P2 panelboards. It is specified for up to 225 A at 240 V AC and requires 6 in of panel unit space.

  • P2 Single-Mount Strap Kit
  • QR 2-Pole/3-Pole Compatibility
  • 225 A Maximum at 240 VAC
  • 6-Inch Panel Unit Space
  • Deadfront Parts and Neutral Lug
  • UL Listed

Product Overview

The Siemens BBKQR1 is a single-mount branch-breaker strap kit for QR-frame 2-pole and 3-pole breakers in Siemens P2 panelboards. It is specified for up to 225 A at 240 V AC and requires 6 in of panel unit space.

Technical Specifications

Product information and specifications for the selected item.

SKU: BBKQR1

Product Information

BrandSiemens
MPNBBKQR1
SKUBBKQR1
UPC / GTIN804766162145
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)225
Voltage240 V AC

Electrical Ratings

Maximum Amperage (A)225
Voltage240 V AC
Phase connector material and finishLong A/C phase connector: 0.25-in copper, tin plated, with tape insulation
Long A/C connector construction0.25-in copper, tin-plated, with tape insulation.
System wiring compatibility1-phase, 2- or 3-wire systems, and 3-phase, 3- or 4-wire systems.
Wiring-system application2-pole QR: 1-phase, 2- or 3-wire; 3-pole QR: 3-phase, 3- or 4-wire

Breaker Configuration

Series TypeP2
Fastener torque requirements#8-32 Ă— 9/32-in thread-forming screws and 1/4-20 Ă— 2-1/2-in machine screws: 30 lb-in; 1/4-20 Ă— 5/8-in and Ă— 3/4-in thread-forming screws: 72 lb-in.
Branch breaker support construction12-gauge galvanized.
Breaker support gauge and finish12-gauge galvanized
Neutral-lug installationAttach the included branch neutral lug at one of four indicated neutral cross-bus sites when a neutral is present; omit this connection on systems without a neutral.
Deadfront fit requirementsA center strip for dual-mounted breakers over the kit position may require deadfront modification; a blank filler is needed if vacated branch-module space remains unfilled.
Compatible breaker modelsQR2, QRH2, HQR2, HQR2H

Pack & Smart Features

Bundle/SingleBundle
Pack OptionsSingle Item
Breaker inclusionThe breaker is not included and must be purchased separately.
Included deadfront componentsIncludes a QR branch deadfront plate and QR breaker deadfront escutcheon.

Certifications

Certifications and ListingsUL Listed

Dimensions & Weight

Height (in.)4.5
Width (in.)8.6
Length (in.)13.7
Weight (lb.)3.7
Branch unit space required6 in
Kit locating incrementDimension D must be a multiple of 3 (0, 3, 6, 9, etc.); add 0.25 when measuring from the bus support.
Breaker connection-hole spacing1.50 in