Siemens Power Mod 800A 1-Phase Standard Tap Box Module, 120/240VAC, NEMA 3R

0 Reviews
SKU
WTB1800CU

The Siemens WTB1800CU is a Power Mod standard tap box module for 1-phase, 3-wire 120/240 VAC service, rated 800 A with a 1200 A thru-bus rating. It has a NEMA 3R enclosure, a 100 kA AIC rating, and top/bottom feed entry for overhead or underground feed.

  • 800 A Module, 1200 A Thru-Bus
  • 1-Phase, 3-Wire, 120/240 VAC
  • 100 kA AIC Rating
  • NEMA 3R Enclosure
  • Overhead or Underground Feed
  • Two Sets of Line-Side Studs

Product Overview

The Siemens WTB1800CU is a Power Mod standard tap box module for 1-phase, 3-wire 120/240 VAC service, rated 800 A with a 1200 A thru-bus rating. It has a NEMA 3R enclosure, a 100 kA AIC rating, and top/bottom feed entry for overhead or underground feed.

Technical Specifications

Product information and specifications for the selected item.

SKU: WTB1800CU

Product Information

BrandSiemens
MPNWTB1800CU
SKUWTB1800CU
UPC / GTIN00040892153170
CategoryMetering Equipment

Key Specs

Monitoring Primary Rated Current800 A
Monitoring Rated Power120/240 VAC
Monitoring Supply Voltage120-240 VAC
NEMA Enclosure RatingNEMA 3R

Monitoring & Electrical

Monitoring Primary Rated Current800 A
Monitoring Rated Power120/240 VAC
Monitoring Supply Voltage120-240 VAC
AIC rating100K AIC
Overcurrent protectionNo overcurrent protection is provided.
Line/load applicationLine- and load-side capable; service entrance and sub-feed rated.
Thru-bus rating1200 A

Configuration & Interface

ComponentAccessories
Suitability for operationGarden-style, meter rise, and high rise
Line-side lug provisionsLugs are not included; NEMA II stud-pattern compression lugs must be installed by the user or utility.
Feed entry configurationTop/bottom
Application suitabilityGarden-style, meter rise, high rise
Line-side stud arrangement2 sets of 2 studs
Line-side connections2 sets of 2 studs; lugs not included
Knockout diagramT-2
Service feed optionsOverhead or underground (OH/UG)
Feed-direction adjustmentInvertible; rotate the module to point hub openings in the desired feed direction.

Ratings & Approvals

NEMA Enclosure RatingNEMA 3R
Monitoring ApprovalUL
UL standardUL-67
Enclosure construction and finishG90 galvanized steel with ANSI 61 paint.
Hardware materialSwing latches and rivets are stainless steel.
Enclosure materialG90 galvanized steel
Service equipment suitabilitySuitable for service-equipment use, subject to conditions in the wiring diagram.

Dimensions & Weight

Weight (lb.)69

Product Documents

  • Multi-Family Metering Solutions: PowerMod and Uni-PAK — Selection & Application Guide Other Open / download file
  • Installation Instructions for Power Mod with QuickSystem — Modular Metering Series WB, WEB, WS, WES, WTB, WET, WMM, WMT, WML and WMK (P/N 4819950, Rev. A) Installation manual Open / download file
  • Data sheet US2:WTB1800CU — MODMTR TAPBOX 800A 1PH 3R 100K TOP/BTM Spec sheet Open / download file

Your cart

0 products 0 units

Your cart is empty.

Add products as you browse, then review them here.