Siemens SENTRON 3VA4 20A 1-Pole Molded-Case Circuit Breaker, 125A Frame, 25kAIC@277V

0 Reviews
SKU
3VA4120-4ED14-0AA0

The Siemens SENTRON 3VA4 is a UL-listed, 20 A single-pole molded-case circuit breaker with a 125 A frame and a specified 415 V AC rating. It has a TM210 T-M trip, a fixed 15×In short-circuit setting, bolt-on mounting with a clamp connection, and a specified 25 kAIC interrupting capacity at 277 V.

  • 20 A Single-Pole Rating
  • 25 kAIC at 277 V
  • 415 V AC Rating
  • 125 A Frame
  • TM210 T-M Trip
  • Bolt-On Mounting, Clamp Connection

The Siemens SENTRON 3VA4 is a UL-listed, 20 A single-pole molded-case circuit breaker with a 125 A frame and a specified 415 V AC rating. It has a TM210 T-M trip, a fixed 15×In short-circuit setting, bolt-on mounting with a clamp connection, and a specified 25 kAIC interrupting capacity at 277 V.

Product Overview

The Siemens SENTRON 3VA4 is a UL-listed, 20 A single-pole molded-case circuit breaker with a 125 A frame and a specified 415 V AC rating. It has a TM210 T-M trip, a fixed 15×In short-circuit setting, bolt-on mounting with a clamp connection, and a specified 25 kAIC interrupting capacity at 277 V.

  • 20 A Single-Pole Rating
  • 25 kAIC at 277 V
  • 415 V AC Rating
  • 125 A Frame
  • TM210 T-M Trip
  • Bolt-On Mounting, Clamp Connection

Technical Specifications

Product information and specifications for the selected item.

SKU: 3VA4120-4ED14-0AA0

Product Information

BrandSENTRON
MPN3VA4120-4ED14-0AA0
SKU3VA4120-4ED14-0AA0
UPC / GTIN804766941764
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)20
Voltage415 V
Interruption TypeStandard Trip
Breaker TypeStandard
Mounting TypeBolt-On
Neutral Connection TypeNon-Neutral

Electrical Ratings

Maximum Amperage (A)20
Voltage415 V
Interruption TypeStandard Trip
Mechanical service life15,000 typical operating cycles
Operational current derating at elevated temperatures19 at 50–55 °C; 18 at 60–65 °C; 17 at 70 °C
Instantaneous short-circuit protection setting (Ii)Fixed at 15 × In
Maximum power loss2.8 W
Storage temperature range-40 to 80 °C
L-trip delay time (tr)1 (minimum and maximum) s
Operating ambient temperature range-25 to 70 °C
UL 489 interrupting capacity at 347 V AC14 kA
UL 489 interrupting capacity at 120 V AC65 kA
Electrical endurance8,000 at 480 V; 4,000 at 600 V operating cycles
100%-rated under UL 489No

Breaker Configuration

Breaker TypeStandard
Mounting TypeBolt-On
Neutral Connection TypeNon-Neutral
Series Type3VA4
Overcurrent release modelTM210
Stranded conductor terminal range1 × 14–8 AWG
Reverse-feed suitabilitySuitable for reverse-feed applications
Overcurrent release protection functionLI
Ground-fault monitoringNot included
Overcurrent release designationTM210 / FTFM
CO auxiliary contacts0 contacts
Main-current terminal arrangementInfeed side: low tab; output side: circular conductor connection
Bottom connection surface finishTin

Pack & Smart Features

Bundle/SingleSingle Product
Pack OptionsSingle Item

Certifications

Certifications and ListingsUL Listed
Front ingress protection ratingIP40
HACR application ratingYes
Switching-duty application ratingYes
HID application ratingYes

Dimensions & Weight

Height (in.)5.094
Width (in.)1
Length (in.)3.63
Weight (lb.)0.617

Product Documents

Your cart