Skip to content

Siemens SENTRON 3VA4 3-Pole 60A Class H Molded-Case Circuit Breaker

0 Reviews
SKU
3VA41606ED340AA0

The Siemens SENTRON 3VA4 (3VA41606ED340AA0) is a UL-listed, three-pole, 60 A molded-case circuit breaker rated 600 V AC, with Class H interrupting capacity of 65 kAIC at 480 V AC. It has a TM210 T-M trip, bolt-on mounting, a low-tab infeed, and lugs installed on the load side only.

  • 3-Pole, 60 A Rating
  • 600 V AC Rating
  • Class H, 65 kAIC at 480 V
  • TM210 T-M Trip
  • Low-Tab Infeed, Load-Side Lugs
  • Bolt-On Mounting

The Siemens SENTRON 3VA4 (3VA41606ED340AA0) is a UL-listed, three-pole, 60 A molded-case circuit breaker rated 600 V AC, with Class H interrupting capacity of 65 kAIC at 480 V AC. It has a TM210 T-M trip, bolt-on mounting, a low-tab infeed, and lugs installed on the load side only.

Product Overview

The Siemens SENTRON 3VA4 (3VA41606ED340AA0) is a UL-listed, three-pole, 60 A molded-case circuit breaker rated 600 V AC, with Class H interrupting capacity of 65 kAIC at 480 V AC. It has a TM210 T-M trip, bolt-on mounting, a low-tab infeed, and lugs installed on the load side only.

  • 3-Pole, 60 A Rating
  • 600 V AC Rating
  • Class H, 65 kAIC at 480 V
  • TM210 T-M Trip
  • Low-Tab Infeed, Load-Side Lugs
  • Bolt-On Mounting

Technical Specifications

Product information and specifications for the selected item.

SKU: 3VA41606ED340AA0

Product Information

BrandSiemens
MPN3VA41606ED340AA0
SKU3VA41606ED340AA0
UPC / GTIN804766944024
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)60
Voltage600 V AC
Interruption TypeStandard Trip
Breaker TypeStandard
Mounting TypeBolt-On
Neutral Connection TypeNon-Neutral

Electrical Ratings

Maximum Amperage (A)60
Voltage600 V AC
Interruption TypeStandard Trip
Operating ambient temperature range-25 to 70 °C
Operational current at 65 °C54 A
Operational current at 50 °C58 A
Operational current at 60 °C55 A
Operational current at 55 °C56 A
Storage temperature range-40 to 80 °C
Operational current at 45 °C59 A
Operational current by ambient temperature59 at 45 °C; 58 at 50 °C; 56 at 55 °C; 55 at 60 °C; 54 at 65 °C; 53 at 70 °C
Instantaneous short-circuit setting (Ii)10 Ă— In, permanently set
Short-circuit trip setting (Ii)10 x In
Maximum power loss13.9 W
Power loss per pole at rated current in hot AC operation4.63 W
L-trip delay with I²t characteristic1 (minimum and maximum) s

Breaker Configuration

Breaker TypeStandard
Mounting TypeBolt-On
Neutral Connection TypeNon-Neutral
Series Type3VA4
Ground-fault monitoringWithout
Connection surface finishTin
Auxiliary changeover contacts0 contacts
Mechanical service life15,000 (typical) cycles
Overcurrent release modelTM210
Output-side connectionCircular conductor connection
Infeed-side connectionLow tab
Overcurrent protection functionLI
Connectable conductor size1 Ă— 8 AWG to 3/0 AWG, stranded round conductor

Pack & Smart Features

Bundle/SingleSingle Product
Pack OptionsSingle Item

Certifications

Certifications and ListingsUL Listed
Front protection classIP40
UL 489 100%-rated breakerNo

Dimensions & Weight

Height (in.)5.09
Width (in.)3
Length (in.)3.63
Weight (lb.)1.638

Product Documents

Your cart

0 products 0 units

Your cart is empty.

Add products as you browse, then review them here.