Siemens SENTRON 3VA4 Class H 125-Frame 3-Pole Circuit Breaker
0 Reviews
SKU
3VA4130-6ED34-0AA0
The Siemens SENTRON 3VA4130-6ED34-0AA0 is a bolt-on, 30 A, three-pole 3VA4 Class H 125-frame molded-case circuit breaker with a thermal-magnetic TM210 LI release. Rated 600Y/347 V, it has an interrupting capacity of 25 kAIC at 600Y/347 V and 65 kAIC at 480 V, and is UL Listed and cUL Listed.
30 A current rating
Three-pole configuration
600Y/347 V rating
Voltage-specific interrupting capacity
TM210 thermal-magnetic LI release
Bolt-on mounting
The Siemens SENTRON 3VA4130-6ED34-0AA0 is a bolt-on, 30 A, three-pole 3VA4 Class H 125-frame molded-case circuit breaker with a thermal-magnetic TM210 LI release. Rated 600Y/347 V, it has an interrupting capacity of 25 kAIC at 600Y/347 V and 65 kAIC at 480 V, and is UL Listed and cUL Listed.
The Siemens SENTRON 3VA4130-6ED34-0AA0 is a bolt-on, 30 A, three-pole 3VA4 Class H 125-frame molded-case circuit breaker with a thermal-magnetic TM210 LI release. Rated 600Y/347 V, it has an interrupting capacity of 25 kAIC at 600Y/347 V and 65 kAIC at 480 V, and is UL Listed and cUL Listed.
30 A current rating
Three-pole configuration
600Y/347 V rating
Voltage-specific interrupting capacity
TM210 thermal-magnetic LI release
Bolt-on mounting
Technical Specifications
Product information and specifications for the selected item.
SKU: 3VA4130-6ED34-0AA0
Product Information
Brand
Siemens
MPN
3VA4130-6ED34-0AA0
SKU
3VA4130-6ED34-0AA0
UPC / GTIN
00804766943720
Category
Circuit Breakers
Key Specs
Maximum Amperage (A)
30
Voltage
600 V
Interruption Type
Standard Trip
Breaker Type
Standard
Mounting Type
Bolt-On
Neutral Connection Type
Non-Neutral
Electrical Ratings
Maximum Amperage (A)
30
Voltage
600 V
Interruption Type
Standard Trip
Overcurrent-release protection function
LI
Mechanical service life
15,000 operating cycles (typical)
Electrical endurance
8,000 cycles at 480 V; 4,000 cycles at 600 V operating cycles
Short-circuit protection setting
Ii = 10 × In, permanently set
Maximum power loss
9 W maximum
Additional UL 489 current-breaking capacities
100 at 240 V; 65 at 480Y/277 V and 480 V kA
UL 489 interrupting capacity at alternate voltages
100 kA at 240 V; 65 kA at 480Y/277 V; 65 kA at 480 V
UL 489 100%-rated breaker status
No
Ground-fault functions
Ground-fault monitoring: without; grounding protection: no
Operating and storage temperature range
Operating: −25 to 70 °C; storage: −40 to 80 °C
L-tripping delay (tr)
tr delay limits: 1 s minimum and 1 s maximum
Operating ambient temperature range
-25 to 70 °C
Power loss per pole
3 W per pole at rated current in hot AC operating state
Operational current derating above 40°C
29 A at 45°C and 50°C; 28 A at 55°C; 27 A at 60°C and 65°C; 26 A at 70°C