Skip to content

Siemens SENTRON 3VA4 Molded-Case Circuit Breaker, UL Frame 125, 3-Pole 45A, Class H, TM210

0 Reviews
SKU
3VA4145-6ED34

The Siemens SENTRON 3VA4 (3VA4145-6ED34) is a three-pole, 45 A molded-case circuit breaker with a 600 V AC rating, UL Frame 125, and Class H interrupting capacity of 65 kA at 480 V. It has a TM210 T-M trip with fixed instantaneous short-circuit pickup at 10Ă— In (450 A), bolt-on mounting, and UL and cUL listings.

  • Three-pole, 45 A rating
  • 600 V AC rating
  • Class H, 65 kA at 480 V
  • TM210 T-M trip
  • Fixed 450 A instantaneous pickup
  • Bolt-on mounting

The Siemens SENTRON 3VA4 (3VA4145-6ED34) is a three-pole, 45 A molded-case circuit breaker with a 600 V AC rating, UL Frame 125, and Class H interrupting capacity of 65 kA at 480 V. It has a TM210 T-M trip with fixed instantaneous short-circuit pickup at 10Ă— In (450 A), bolt-on mounting, and UL and cUL listings.

Product Overview

The Siemens SENTRON 3VA4 (3VA4145-6ED34) is a three-pole, 45 A molded-case circuit breaker with a 600 V AC rating, UL Frame 125, and Class H interrupting capacity of 65 kA at 480 V. It has a TM210 T-M trip with fixed instantaneous short-circuit pickup at 10Ă— In (450 A), bolt-on mounting, and UL and cUL listings.

  • Three-pole, 45 A rating
  • 600 V AC rating
  • Class H, 65 kA at 480 V
  • TM210 T-M trip
  • Fixed 450 A instantaneous pickup
  • Bolt-on mounting

Technical Specifications

Product information and specifications for the selected item.

SKU: 3VA4145-6ED34

Product Information

BrandSiemens
MPN3VA4145-6ED34
SKU3VA4145-6ED34
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)45
Voltage600 V
Interruption TypeStandard Trip
Breaker TypeStandard
Mounting TypeBolt-On
Neutral Connection TypeNon-Neutral

Electrical Ratings

Maximum Amperage (A)45
Voltage600 V
Interruption TypeStandard Trip
UL 489 current-breaking capacity240 V: 100; 480Y/277 V: 65; 480 V: 65; 600Y/347 V: 25 kA
Power lossMaximum 10.6; 3.53 per pole at rated current in hot operating state W
Grounding protectionNo ground-fault protection
Storage temperature range-40 °C to 80 °C
Operational current above 40 °C45 °C: 44; 50 °C: 43; 55 °C: 43; 60 °C: 42; 65 °C: 41; 70 °C: 40 A
Overcurrent release protection functionLI
Mechanical and electrical enduranceTypical mechanical: 15,000; electrical: 8,000 at 480 V and 4,000 at 600 V cycles
Mechanical service life15,000 operating cycles (typical)
Instantaneous short-circuit trip setting (Ii)450 A
Ground-fault featuresGround-fault monitoring: without; grounding protection: no
Operating current by ambient temperature44 A at 45 °C; 43 A at 50 °C; 43 A at 55 °C; 42 A at 60 °C; 41 A at 65 °C; 40 A at 70 °C
L-tripping delay time (tr) with I2t characteristic1 s minimum; 1 s maximum
100%-rated breaker statusNot 100%-rated
Operating ambient temperature range-25 °C to 70 °C
Operating and storage temperature limitsOperation: -25 to 70; storage: -40 to 80 °C
Fixed short-circuit pickup (Ii)Permanently set at 10 x In

Breaker Configuration

Breaker TypeStandard
Mounting TypeBolt-On
Neutral Connection TypeNon-Neutral
Series Type3VA4
Bottom connection surface finishTin
Main-circuit terminal arrangementInfeed: low tab; output: circular conductor connection
Auxiliary changeover contacts0 contacts
Connectable conductor range1 stranded conductor, 8 AWG–3/0 AWG
Main-circuit connection arrangementInfeed side: low tab; output side: circular conductor connection
Connectable conductor size1 x 8 AWG to 3/0, stranded round conductor
Release and indicator componentsNo undervoltage release, voltage trigger, or trip indicator

Pack & Smart Features

Bundle/SingleSingle Product

Certifications

Certifications and ListingscUL Listed, UL Listed
Front ingress protectionIP40 on the front

Dimensions & Weight

Height (in.)5.094
Width (in.)3
Length (in.)3.634
Weight (lb.)1.638

Product Documents

Your cart

0 products 0 units

Your cart is empty.

Add products as you browse, then review them here.