Siemens SENTRON 3VA4 UL 20A 1-Pole Class-S Molded-Case Circuit Breaker
0 Reviews
SKU
3VA4120--4ED14
The Siemens SENTRON 3VA4 is a UL-listed, Class-S molded-case circuit breaker rated 20 A with one pole and a 125 A frame. It uses a TM210 thermal-magnetic trip, has 25 kA AC short-circuit breaking capacity at 277 V, and is listed as a compatible 3VA branch breaker for RapidSBx switchboards.
20 A, single-pole rating
25 kA AC at 277 V
125 A frame
TM210 thermal-magnetic trip
Bolt-on mounting
14–8 AWG conductor range
The Siemens SENTRON 3VA4 is a UL-listed, Class-S molded-case circuit breaker rated 20 A with one pole and a 125 A frame. It uses a TM210 thermal-magnetic trip, has 25 kA AC short-circuit breaking capacity at 277 V, and is listed as a compatible 3VA branch breaker for RapidSBx switchboards.
The Siemens SENTRON 3VA4 is a UL-listed, Class-S molded-case circuit breaker rated 20 A with one pole and a 125 A frame. It uses a TM210 thermal-magnetic trip, has 25 kA AC short-circuit breaking capacity at 277 V, and is listed as a compatible 3VA branch breaker for RapidSBx switchboards.
20 A, single-pole rating
25 kA AC at 277 V
125 A frame
TM210 thermal-magnetic trip
Bolt-on mounting
14–8 AWG conductor range
Technical Specifications
Product information and specifications for the selected item.
SKU: 3VA4120--4ED14
Product Information
Brand
SENTRON
MPN
3VA4120--4ED14
SKU
3VA4120--4ED14
Category
Circuit Breakers
Key Specs
Maximum Amperage (A)
20
Voltage
415 V
Interruption Type
Standard Trip
Breaker Type
Standard
Mounting Type
Bolt-On
Neutral Connection Type
Non-Neutral
Electrical Ratings
Maximum Amperage (A)
20
Voltage
415 V
Interruption Type
Standard Trip
Electrical endurance
8,000 cycles at 480 V; 4,000 cycles at 600 V operating cycles
HID rating
Yes
HACR rating
Yes
UL 489 breaking capacity at 120 V
65 kA
Operational current at elevated ambient temperatures
19 A at 50–55 °C; 18 A at 60–65 °C; 17 A at 70 °C
Instantaneous short-circuit trip setting
Ii = 15 × In; permanently set
Operating ambient temperature
−25 to 70 °C
Maximum power loss
2.8 W
SWD rating
Yes
Storage temperature
−40 to 80 °C
AC short-circuit breaking capacity
65 kA at 120 V; 25 kA at 277 V; 14 kA at 347 V
Mechanical service life
15,000 typical operating cycles
100%-rated breaker marking
No
Front protection rating
IP40
Breaker Configuration
Breaker Type
Standard
Mounting Type
Bolt-On
Neutral Connection Type
Non-Neutral
Series Type
3VA41
Overcurrent protection function
LI
Ground-fault protection
No
RapidSBx switchboard compatibility
Listed as a compatible 3VA branch breaker for RapidSBx switchboards
Connection surface finish
Tin
Connectable conductor size
1 × 14–8 AWG, stranded round conductor
Built-in components
No undervoltage release, voltage trigger, or trip indicator