3VA4195-5ED34-0AA0

The Siemens SENTRON 3VA41 is a UL Listed, bolt-on molded-case circuit breaker rated 15 A, with three poles and a 125 A frame. It has Class M breaking capacity, a TM210 thermal-magnetic trip with fixed Ir/Ii settings, and lugs on the load side only.

  • 15 A Three-Pole Rating
  • Class M Interrupting Ratings
  • 125 A Frame
  • TM210 Thermal-Magnetic Trip
  • Load-Side Lugs Only
  • UL Listed

The Siemens SENTRON 3VA41 is a UL Listed, bolt-on molded-case circuit breaker rated 15 A, with three poles and a 125 A frame. It has Class M breaking capacity, a TM210 thermal-magnetic trip with fixed Ir/Ii settings, and lugs on the load side only.

Product Overview

The Siemens SENTRON 3VA41 is a UL Listed, bolt-on molded-case circuit breaker rated 15 A, with three poles and a 125 A frame. It has Class M breaking capacity, a TM210 thermal-magnetic trip with fixed Ir/Ii settings, and lugs on the load side only.

  • 15 A Three-Pole Rating
  • Class M Interrupting Ratings
  • 125 A Frame
  • TM210 Thermal-Magnetic Trip
  • Load-Side Lugs Only
  • UL Listed

Technical Specifications

Product information and specifications for the selected item.

SKU: 3VA4195-5ED34-0AA0

Product Information

BrandSiemens
MPN3VA4195-5ED34-0AA0
SKU3VA4195-5ED34-0AA0
UPC / GTIN00804766943522
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)15
Voltage600 V
Interruption TypeStandard Trip
Breaker TypeStandard
Mounting TypeBolt-On
Neutral Connection TypeNon-Neutral

Electrical Ratings

Maximum Amperage (A)15
Voltage600 V
Interruption TypeStandard Trip
Power loss per pole at rated current in hot operating state3.27 W
Operational current at elevated ambient temperatures14 A at 50–60 °C; 13 A at 65–70 °C
Maximum power loss9.8 W
Electrical endurance at 480 V8,000 operating cycles
Operating ambient temperature range-25 to 70 °C
L-trip delay with I2t characteristic (minimum and maximum)1 s
UL 489 current breaking capacity at 240 V85 kA
UL 489 current breaking capacity at 480Y/277 V35 kA
Electrical endurance at 600 V4,000 operating cycles
Front protection classIP40
Short-circuit pickupIi = 20 Ă— In, permanently set
Mechanical service life15,000 (typical) operating cycles
UL 489 current breaking capacity at 600Y/347 V18 kA
100%-rated breakerNo
Storage temperature range-40 to 80 °C

Breaker Configuration

Breaker TypeStandard
Mounting TypeBolt-On
Neutral Connection TypeNon-Neutral
Series Type3VA4
Grounding protectionNo
Infeed-side connectionLow tab
Output-side connectionCircular conductor connection
Built-in release and indicator componentsNo undervoltage release, voltage trigger, or trip indicator
Overcurrent-release protection functionLI
Ground-fault monitoringWithout
Bottom connection surface finishTin
Auxiliary CO contacts0
Stranded round-conductor terminal size1 × (14 AWG–8 AWG), stranded

Pack & Smart Features

Bundle/SingleSingle Product
Pack OptionsSingle Item

Certifications

Certifications and ListingsUL Listed

Dimensions & Weight

Height (in.)5.09
Width (in.)3
Length (in.)3.634
Weight (lb.)1.638

Product Documents