Skip to content

Siemens SENTRON 3VA41 20A 3P Class S Molded-Case Circuit Breaker, TM210 T-M Trip

0 Reviews
SKU
3VA4120-4ED34-0AA0

The Siemens SENTRON 3VA41 is a 20 A, three-pole, 600 V AC molded-case circuit breaker with a 125 A frame and Class S breaking capacity. It uses a TM210 thermal-magnetic trip unit with fixed Ir and Ii settings and has bolt-on mounting.

  • 20 A current rating
  • Three-pole configuration
  • 600 V AC rating
  • UL 489 interrupting capacity
  • TM210 thermal-magnetic trip
  • Load-side terminal lugs

The Siemens SENTRON 3VA41 is a 20 A, three-pole, 600 V AC molded-case circuit breaker with a 125 A frame and Class S breaking capacity. It uses a TM210 thermal-magnetic trip unit with fixed Ir and Ii settings and has bolt-on mounting.

Product Overview

The Siemens SENTRON 3VA41 is a 20 A, three-pole, 600 V AC molded-case circuit breaker with a 125 A frame and Class S breaking capacity. It uses a TM210 thermal-magnetic trip unit with fixed Ir and Ii settings and has bolt-on mounting.

  • 20 A current rating
  • Three-pole configuration
  • 600 V AC rating
  • UL 489 interrupting capacity
  • TM210 thermal-magnetic trip
  • Load-side terminal lugs

Technical Specifications

Product information and specifications for the selected item.

SKU: 3VA4120-4ED34-0AA0

Product Information

BrandSiemens
MPN3VA4120-4ED34-0AA0
SKU3VA4120-4ED34-0AA0
UPC / GTIN00804766943560
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)20
Voltage600 V AC
Interruption TypeStandard Trip
Breaker TypeStandard
Mounting TypeBolt-On
Neutral Connection TypeNon-Neutral

Electrical Ratings

Maximum Amperage (A)20
Voltage600 V AC
Interruption TypeStandard Trip
UL 489 interrupting capacity at 600Y/347 V14 kA
Storage temperature-40 to 80 °C
UL 489 interrupting capacity at 480 V25 kA
Operational current by ambient temperature19 at 50–55 °C; 18 at 60–65 °C; 17 at 70 °C
UL 489 interrupting capacity at 480Y/277 V25 kA
Mechanical service life15,000 typical operating cycles
Power loss8.5 maximum; 2.83 per pole at rated current in hot operating state W
Operating ambient temperature-25 to 70 °C
Electrical endurance8,000 at 480 V; 4,000 at 600 V operating cycles
Instantaneous trip setting (Ii)300 A
UL 489 interrupting capacity at 240 V65 kA
100%-rated breaker markingNo

Breaker Configuration

Breaker TypeStandard
Mounting TypeBolt-On
Neutral Connection TypeNon-Neutral
Series Type3VA41
Overcurrent protection functionLI
Installed terminal lugSmall aluminum-body lug for one Cu/Al cable, AWG 14–8 (75 °C wire)
Built-in releases and indicatorsNo undervoltage release, voltage trigger, or trip indicator
Main-circuit output connectionCircular conductor connection
Connection surface finishTin
Connectable conductor1 x 14–8 AWG, stranded round conductor
Ground-fault protectionNo
Main-circuit infeed connectionLow tab
Auxiliary CO contacts0 contacts

Pack & Smart Features

Bundle/SingleSingle Product
Pack OptionsSingle Item

Certifications

Certifications and ListingsUL Listed
Reverse-feed suitabilityUL listed for reverse-feed applications
Front protection ratingIP40
Special application ratingsHACR, HID, and SWD types: Yes

Dimensions & Weight

Height (in.)5.09
Width (in.)3
Length (in.)3.634
Weight (lb.)1.638

Product Documents

Your cart

1 product 1 unit