Skip to content

Siemens SENTRON 3VA5 100A 3-Pole Molded-Case Circuit Breaker, 125A Frame, 25kA at 480V

0 Reviews
SKU
3VA5110-4EC31-0AA0

The Siemens SENTRON 3VA5 is a 100 A, three-pole molded-case circuit breaker with a 125 A frame and a 25 kA interrupting rating at 480 V. It has a TM230/FTAM T-M trip unit, a 690 V voltage rating, and is supplied without lugs.

  • 100 A Rated Current
  • Three-Pole Configuration
  • 25 kA at 480 V
  • 125 A Frame
  • TM230/FTAM T-M Trip Unit
  • Supplied Without Lugs

The Siemens SENTRON 3VA5 is a 100 A, three-pole molded-case circuit breaker with a 125 A frame and a 25 kA interrupting rating at 480 V. It has a TM230/FTAM T-M trip unit, a 690 V voltage rating, and is supplied without lugs.

Product Overview

The Siemens SENTRON 3VA5 is a 100 A, three-pole molded-case circuit breaker with a 125 A frame and a 25 kA interrupting rating at 480 V. It has a TM230/FTAM T-M trip unit, a 690 V voltage rating, and is supplied without lugs.

  • 100 A Rated Current
  • Three-Pole Configuration
  • 25 kA at 480 V
  • 125 A Frame
  • TM230/FTAM T-M Trip Unit
  • Supplied Without Lugs

Technical Specifications

Product information and specifications for the selected item.

SKU: 3VA5110-4EC31-0AA0

Product Information

BrandSiemens
MPN3VA5110-4EC31-0AA0
SKU3VA5110-4EC31-0AA0
UPC / GTIN804766301018
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)100
Voltage690 V
Interruption TypeStandard Trip
Breaker TypeStandard
Mounting TypeDin Rail
Neutral Connection TypeNon-Neutral

Electrical Ratings

Maximum Amperage (A)100
Voltage690 V
Interruption TypeStandard Trip
Power loss per pole at rated current7.6 W/pole
IEC 60947 short-circuit making capacity (Icm)121 kA at 240 V; 75.6 kA at 415 V; 7.5 kA at 690 V
Storage temperature-40 to 80 °C
Rated insulation voltage800 V
IEC 60947 maximum short-circuit breaking capacity (Icu)55 kA at 240 V; 36 kA at 415 V; 5 kA at 690 V
Operating ambient temperature-25 to 70 °C
Electrical endurance8,000 cycles at AC-1 380/415 V; 4,000 at AC-1 690 V; 8,000 at 480 V; 4,000 at 600 V operating cycles
Maximum power loss22.8 W
Operational current at 70 °C87 A
UL 489 interrupting capacity at alternate voltages65 kA at 240 V; 14 kA at 600Y/347 V
Mechanical service life20,000 typical operating cycles

Breaker Configuration

Breaker TypeStandard
Mounting TypeDin Rail
Neutral Connection TypeNon-Neutral
Series Type3VA5
Overcurrent release and protection functionTM230; LI
Front protection classIP40
Main-current connection arrangementWithout connection
Main-circuit connector arrangementWithout connection
Instantaneous trip pickup range (Ii)500–1,000 A
Instantaneous trip setting range (Ii)500–1,000 A (5–10 × In)
Grounding protectionNo
Reverse-feed application suitabilitySuitable for reverse-feed applications
Ground-fault protectionNo
Long-time trip delay (tr, I2t characteristic)1 s

Pack & Smart Features

Bundle/SingleSingle Product

Certifications

Certifications and ListingscUL Listed, ROHS, UL Listed
UL 489 100%-rated breaker designationNo
100%-rated breaker markingNo
UL 489 HACR typeYes

Dimensions & Weight

Height (in.)5.51
Width (in.)3
Length (in.)3.72
Weight (lb.)2.0944

Product Documents

Your cart

1 product 1 unit