The Siemens SENTRON 3VA52205EC31 is a Class M 3VA5 molded-case circuit breaker with three poles, a 200 A rating, and a 250 A frame. It uses a TM230/FTAM thermal-magnetic trip, is rated 690 V AC and 35 kAIC at 480 V, and is UL Listed and cUL Listed.

  • 200 A Rated Current
  • Three-Pole Configuration
  • 35 kAIC at 480 V
  • 690 V AC Rating
  • 250 A Frame
  • TM230/FTAM Thermal-Magnetic Trip

Product Overview

The Siemens SENTRON 3VA52205EC31 is a Class M 3VA5 molded-case circuit breaker with three poles, a 200 A rating, and a 250 A frame. It uses a TM230/FTAM thermal-magnetic trip, is rated 690 V AC and 35 kAIC at 480 V, and is UL Listed and cUL Listed.

Technical Specifications

Product information and specifications for the selected item.

SKU: 3VA52205EC31

Product Information

BrandSiemens
MPN3VA52205EC31
SKU3VA52205EC31
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)200
Voltage690 V AC
Interruption TypeStandard Trip
Breaker TypeStandard
Neutral Connection TypeNon-Neutral

Electrical Ratings

Maximum Amperage (A)200
Voltage690 V AC
Interruption TypeStandard Trip
UL 489 100%-rated statusNot 100%-rated
IEC 60947 ultimate short-circuit breaking capacity (Icu)240 V: 85; 415 V: 55; 690 V: 7 kA
Electrical endurance8,000 cycles at AC-1 / 380/415 V; 8,000 at 480 V; 4,000 at 600 V; 4,000 at AC-1 / 690 V
IEC 60947 short-circuit current making capacity (Icm)240 V: 187; 415 V: 121; 690 V: 11.9 kA
Instantaneous short-circuit pickup range (Ii)1,000–2,000 A
Power loss per pole at rated current in hot AC operation14.17 W
Instantaneous trip setting range (Ii)1,000–2,000 A
L-trip response delay time (tr)1 s
Typical mechanical service life20,000 operating cycles
IEC 60947 maximum short-circuit breaking capacity (Icu)240 V: 85; 415 V: 55; 690 V: 7 kA
Operating ambient temperature range-25 to 70 °C
Operational current at elevated ambient temperatures45 °C: 194 A; 50 °C: 189 A; 55 °C: 183 A; 60 °C: 178 A; 65 °C: 172 A; 70 °C: 167 A
IEC 60947 operating short-circuit current breaking capacity (Ics)240 V: 85; 415 V: 55; 690 V: 7 kA
Maximum power loss43 W
Storage temperature range-40 to 80 °C
UL 489 current breaking capacity600 V: 18 kA
IEC 60947 service short-circuit breaking capacity (Ics)240 V: 85; 415 V: 55; 690 V: 7 kA
UL 489 breaking capacity at additional test voltages240 V: 85; 600 V: 18 kA

Breaker Configuration

Breaker TypeStandard
Neutral Connection TypeNon-Neutral
Series Type3VA5
Overcurrent-release protection functionLI
Included trip componentsNo undervoltage release, voltage trigger, or trip indicator
Main-circuit lugs includedNo
Grounding protectionNo
Front protection classIP40
Auxiliary changeover (CO) contacts0 contacts

Pack & Smart Features

Bundle/SingleSingle Product
Pack OptionsSingle Item

Certifications

Certifications and ListingscUL Listed, UL Listed

Dimensions & Weight

Height (in.)7.28
Width (in.)4.13
Length (in.)4.21
Weight (lb.)4.47