The Siemens SENTRON 3VA614 is a 40 A, three-pole 3VA61 molded-case circuit breaker rated 600 V AC. It has a 150 A frame, Class M breaking capacity, and an ETU350 LSI electronic trip unit; short-circuit interrupting capacity is 35 kAIC at 480 V and 18 kAIC at 600 V. The breaker is supplied without lugs.

  • 40 A, Three-Pole Rating
  • 600 V AC Rating
  • 35/18 kAIC by Voltage
  • ETU350 LSI Trip Unit
  • 150 A Frame, Class M
  • Supplied Without Lugs

The Siemens SENTRON 3VA614 is a 40 A, three-pole 3VA61 molded-case circuit breaker rated 600 V AC. It has a 150 A frame, Class M breaking capacity, and an ETU350 LSI electronic trip unit; short-circuit interrupting capacity is 35 kAIC at 480 V and 18 kAIC at 600 V. The breaker is supplied without lugs.

Product Overview

The Siemens SENTRON 3VA614 is a 40 A, three-pole 3VA61 molded-case circuit breaker rated 600 V AC. It has a 150 A frame, Class M breaking capacity, and an ETU350 LSI electronic trip unit; short-circuit interrupting capacity is 35 kAIC at 480 V and 18 kAIC at 600 V. The breaker is supplied without lugs.

  • 40 A, Three-Pole Rating
  • 600 V AC Rating
  • 35/18 kAIC by Voltage
  • ETU350 LSI Trip Unit
  • 150 A Frame, Class M
  • Supplied Without Lugs

Technical Specifications

Product information and specifications for the selected item.

SKU: 3VA614

Product Information

BrandSiemens
MPN3VA614
SKU3VA614
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)40
Voltage600 V AC
Interruption TypeStandard Trip
Breaker TypeStandard
Neutral Connection TypeNon-Neutral

Electrical Ratings

Maximum Amperage (A)40
Voltage600 V AC
Interruption TypeStandard Trip
IEC 60947-2 short-circuit making capacity (Icm)187 at 240 V; 121 at 415 V; 3.8 at 690 V kA
Active power loss per device at rated current2.4 W
II short-circuit protection setting12 Ă— In
Instantaneous pickup threshold (Ii)Fixed at 480 (12 Ă— In)
Electrical endurance at 50/60 Hz9,000 at 380/415 V (AC-1), 480 V and 600 V; 5,000 at 690 V (AC-1) switching cycles
Short-time pickup setting (Isd)1.5–10 × Ir
Frame size150 A
Storage temperature range-40 to 80 °C
Typical mechanical service life20,000 switching cycles
IEC 60947-2 service breaking capacity (Ics)85 at 240 V; 55 at 415 V; 2.5 at 690 V kA
Short-circuit protection ISD setting range1.5–10 × Ir
Short-time delay selector settings0, 0.08, 0.15, 0.22, 0.3, and 0.4 s
100%-rated breakerNo
Short-circuit breaking capacity by voltage100 at 240 V; 35 at 480Y/277 V and 480 V; 18 at 600Y/347 V and 600 V kA
IEC 60947-2 ultimate breaking capacity (Icu)85 at 240 V; 55 at 415 V; 2.5 at 690 V kA
UL 489 breaking capacity100 at 240 V; 18 at 600 Y/347 V and 600 V kA
Ambient operating temperature range-25 to 70 °C
UL 489 100%-rated statusNo
Long-time delay selector settings0.5, 0.75, 1, 2, 3, 5, 8, 10, 14, and 17 s
Overload protection IR setting range16–40 A

Breaker Configuration

Breaker TypeStandard
Neutral Connection TypeNon-Neutral
Series Type3VA61
Auxiliary CO contacts0 contacts

Pack & Smart Features

Bundle/SingleSingle Product
Pack OptionsSingle Item
Other measurement functionNo
Communication functionNo

Certifications

Certifications and ListingsCSA Certified, UL Listed
Front protection ratingIP40

Dimensions & Weight

Height (in.)7.8
Width (in.)4.13
Length (in.)4.21
Weight (lb.)4.53

Product Documents

  • Molded Case Circuit Breakers — SPEEDFAX Product Catalog, Section 7 Other Open / download file
  • Circuit Breaker with Electronic Trip Units of the 3 Series — Operating Instructions, A5E03012798021-03 Installation manual Open / download file
  • Data sheet — 3VA6140-5HN31-0AA0, Circuit Breaker 3VA6 Spec sheet Open / download file

Your cart

0 products 0 units

Your cart is empty.

Add products as you browse, then review them here.