Skip to content

Siemens SENTRON 3VA62 250A 3-Pole MCCB, Class M, ETU350 LSI, Without Lugs

0 Reviews
SKU
3VA6225

The Siemens SENTRON 3VA62 (3VA6225) is a 250 A, three-pole molded-case circuit breaker with Class M breaking capacity and an ETU350 LSI electronic trip unit. It is rated 690 V AC and has bolt-on mounting; this version is supplied without lugs.

  • 250 A current rating
  • Three-pole configuration
  • ETU350 LSI electronic trip
  • Class M breaking capacity
  • 690 V AC voltage rating
  • Bolt-on mounting without lugs

Product Overview

The Siemens SENTRON 3VA62 (3VA6225) is a 250 A, three-pole molded-case circuit breaker with Class M breaking capacity and an ETU350 LSI electronic trip unit. It is rated 690 V AC and has bolt-on mounting; this version is supplied without lugs.

Technical Specifications

Product information and specifications for the selected item.

SKU: 3VA6225

Product Information

BrandSiemens
MPN3VA6225
SKU3VA6225
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)250
Voltage690 V
Interruption TypeStandard Trip
Breaker TypeStandard
Mounting TypeBolt-On
Neutral Connection TypeNon-Neutral

Electrical Ratings

Maximum Amperage (A)250
Voltage690 V
Interruption TypeStandard Trip
IEC 60947 Icu at 415 V55 kA
IEC 60947-2 making capacity (Icm)187 at 240 V; 121 at 415 V; 4.5 at 690 V kA
Power loss42 maximum; 14 per pole at rated current in hot operating state W
UL 489 interrupting capacity100 at 240 V; 35 at 480 V; 18 at 600 V kA
UL 489 short-circuit breaking capacity at 240 V100 kA
Electrical endurance12,000 at AC-1 380/415 V; 8,400 at AC-1 690 V; 12,000 at 480 V; 8,400 at 600 V operating cycles
Current derating at elevated temperatures241 at 55 °C; 232 at 60 °C; 222 at 65 °C; 213 at 70 °C
IEC 60947 Ics at 415 V55 kA
IEC 60947-2 breaking capacity (Icu/Ics)85 at 240 V; 55 at 415 V; 3 at 690 V (Icu and Ics) kA
Ambient temperature rangeOperating: −25 to 70; storage: −40 to 80 °C
100%-rated breaker statusNo

Breaker Configuration

Breaker TypeStandard
Mounting TypeBolt-On
Neutral Connection TypeNon-Neutral
Series Type3VA62
Trip-setting interfaceParameters are selected using a setting knob
Short-time delay setting (tsd)0.0001–0.4 s
Reverse-feed suitabilityReverse-feed applications permitted
Long-time pickup setting (Ir)100–250 A
Long-time delay setting (tr)0.5–13 s
Mechanical service life25,000 operating cycles
Ground-fault protectionNo ground-fault monitoring; grounding protection: No
Short-time pickup setting (Isd)375–2,500 A
Instantaneous pickup (Ii)2,500; fixed at 10 × In

Pack & Smart Features

Bundle/SingleSingle Product
Communication and measurement functionsNo communication function; no other measurement function

Certifications

Certifications and ListingsCSA Certified, cUL Listed, ROHS, TUV Listed, UL Listed
Environmental Product Declaration availableYes
Front-face protection ratingIP40
Total global warming potential61.814 kg CO2 eq

Dimensions & Weight

Height (in.)7.8
Width (in.)4.13
Length (in.)3.39
Weight (lb.)4.861

Product Documents

Your cart

0 products 0 units

Your cart is empty.

Add products as you browse, then review them here.