The Siemens SENTRON E3RMD63B600 is an enclosed 600 A, three-pole molded-case circuit breaker with a 600 V AC rating, MD frame and standard breaking capacity. The assembly includes an interchangeable thermal-magnetic trip unit, a sheet-steel NEMA Type 3R enclosure and standard line/load pressure wire connectors; the breaker is UL Listed.

  • 600 A, three-pole breaker
  • 600 V AC rating
  • 25 kA at 600 V AC
  • NEMA Type 3R steel enclosure
  • Interchangeable thermal-magnetic trip unit
  • Standard line/load connectors included

Product Overview

The Siemens SENTRON E3RMD63B600 is an enclosed 600 A, three-pole molded-case circuit breaker with a 600 V AC rating, MD frame and standard breaking capacity. The assembly includes an interchangeable thermal-magnetic trip unit, a sheet-steel NEMA Type 3R enclosure and standard line/load pressure wire connectors; the breaker is UL Listed.

Technical Specifications

Product information and specifications for the selected item.

SKU: E3RMD63B600

Product Information

BrandSiemens
MPNE3RMD63B600
SKUE3RMD63B600
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)600
Voltage600 V
Interruption TypeStandard Trip
Breaker TypeStandard
Mounting TypeBolt-On
Neutral Connection TypeNon-Neutral

Electrical Ratings

Maximum Amperage (A)600
Voltage600 V
Interruption TypeStandard Trip
DC interrupting rating and application condition25 kA at 500 V DC (3-pole); rated for an ungrounded UPS application when wired in zig-zag through the breaker
Rated frequency50/60 Hz
RMS symmetrical AC interrupting ratings65 kA at 240 V AC; 50 kA at 480 V AC; 25 kA at 600 V AC
Continuous-current rating reference temperature40 °C
Operating ambient temperature range-25 to 75 °C
Interrupting rating25 kA

Breaker Configuration

Breaker TypeStandard
Mounting TypeBolt-On
Neutral Connection TypeNon-Neutral
Series TypeMD6
Included assembly componentsTrip unit, enclosure, and standard line/load pressure wire connectors are included with the breaker frame.
Enclosure materialSheet steel
Thermal-trip reset behaviorAfter a thermal trip, reset is not possible until the thermal element cools.
Line/load lug conductor range1/0–500 kcmil Cu/Al; 1–3 cables per TA3K500 lug
Manual trip-test functionThe PUSH-TO-TRIP button checks trip function and manually exercises the operating mechanism.
Handle indication positionsThe handle indicates ON, OFF, and TRIP; TRIP is between ON and OFF.