The Siemens GF223NRA is a 100 A, 2-pole, 240 V fused outdoor safety switch with a galvanized-steel enclosure. Listed details include service-entrance suitability, mechanical-lug conductor ranges and fuse-dependent short-circuit ratings.
100 A, 2-Pole, 240 V
Fuse-Dependent AIC Ratings
Mechanical Lug Wire Ranges
240 V AC Motor Ratings
Service-Entrance Suitability
Rain and Sleet Protection
The Siemens GF223NRA is a 100 A, 2-pole, 240 V fused outdoor safety switch with a galvanized-steel enclosure. Listed details include service-entrance suitability, mechanical-lug conductor ranges and fuse-dependent short-circuit ratings.
The Siemens GF223NRA is a 100 A, 2-pole, 240 V fused outdoor safety switch with a galvanized-steel enclosure. Listed details include service-entrance suitability, mechanical-lug conductor ranges and fuse-dependent short-circuit ratings.
100 A, 2-Pole, 240 V
Fuse-Dependent AIC Ratings
Mechanical Lug Wire Ranges
240 V AC Motor Ratings
Service-Entrance Suitability
Rain and Sleet Protection
Technical Specifications
Product information and specifications for the selected item.
SKU: GF223NRA
Product Information
Brand
Siemens
SKU
GF223NRA
Category
Disconnects & Safety Switches
Key Specs
Maximum Amperage (A)
100
Maximum Wattage (W)
0
Phase Type
1 Phase
Disconnect Type
Safety Switch
NEMA Enclosure Rating
NEMA 3R
Switch Ratings
Maximum Amperage (A)
100
Maximum Wattage (W)
0
Phase Type
1 Phase
Fuse-dependent short-circuit rating
10,000 with Class H fuses; 100,000 with Class R fuses. AIC
Grounded B-phase compatibility
Suitable for grounded B-phase system applications.
Short-circuit interrupting rating
10,000 with Class H fuses; 100,000 with Class R fuses AIC
Mechanical lug wire ranges
Line/load and neutral: #12–1/0 AWG aluminum or #14–1/0 AWG copper; ground: #14–4 AWG.
Conductor temperature rating
For 60°C or 75°C conductors.
Motor horsepower ratings
At 240 V AC: 1-phase/3-wire, 7.5 hp standard and 15 hp maximum; 3-phase/3-wire, 15 hp standard and 30 hp maximum. At 250 V DC: 20 hp. Standard ratings use non-time-delay fuses; maximum ratings use time-delay fuses.
Disconnect Configuration
Disconnect Type
Safety Switch
Fused
Fused
Blade design
Double-break visible blade design.
Serviceability
Modular design allows quick and easy replacement of parts.
Padlockable cover latch and multiple padlock provisions on the handle.
Cover interlock
Single cover interlock.
Door opening
Side-opening door opens more than 180°.
Enclosure & Certifications
NEMA Enclosure Rating
NEMA 3R
Certifications and Listings
UL Listed
Enclosure thickness
0.054 in (17 gauge).
Enclosure finish
ANSI Grey #61 paint.
Enclosure material
Galvanized steel.
Service-entrance suitability
Suitable for use as service entrance equipment.
Outdoor exposure protection
Provides a degree of protection against falling rain and sleet and must remain undamaged by ice formation; not intended to protect against dust, internal condensation, or internal icing.
Rain-entry design
Double-overlap enclosure door top helps limit rain entry.
Dimensions & Weight
Height (in.)
23.46
Width (in.)
11.67
Length (in.)
8.7
Weight (lb.)
20.6
Wire-bending space
Fused configuration: line side 6.07 in (154 mm); load side 8.10 in (206 mm). in (mm)