Skip to content

Siemens VBII General-Duty Fusible Safety Switch, 100A, 2-Pole, 240V, 3-Wire, Type 3R

0 Reviews
SKU
GF223NRA

The Siemens GF223NRA is a 100 A, 2-pole, 240 V fused outdoor safety switch with a galvanized-steel enclosure. Listed details include service-entrance suitability, mechanical-lug conductor ranges and fuse-dependent short-circuit ratings.

  • 100 A, 2-Pole, 240 V
  • Fuse-Dependent AIC Ratings
  • Mechanical Lug Wire Ranges
  • 240 V AC Motor Ratings
  • Service-Entrance Suitability
  • Rain and Sleet Protection

The Siemens GF223NRA is a 100 A, 2-pole, 240 V fused outdoor safety switch with a galvanized-steel enclosure. Listed details include service-entrance suitability, mechanical-lug conductor ranges and fuse-dependent short-circuit ratings.

Product Overview

The Siemens GF223NRA is a 100 A, 2-pole, 240 V fused outdoor safety switch with a galvanized-steel enclosure. Listed details include service-entrance suitability, mechanical-lug conductor ranges and fuse-dependent short-circuit ratings.

  • 100 A, 2-Pole, 240 V
  • Fuse-Dependent AIC Ratings
  • Mechanical Lug Wire Ranges
  • 240 V AC Motor Ratings
  • Service-Entrance Suitability
  • Rain and Sleet Protection

Technical Specifications

Product information and specifications for the selected item.

SKU: GF223NRA

Product Information

BrandSiemens
SKUGF223NRA
CategoryDisconnects & Safety Switches

Key Specs

Maximum Amperage (A)100
Maximum Wattage (W)0
Phase Type1 Phase
Disconnect TypeSafety Switch
NEMA Enclosure RatingNEMA 3R

Switch Ratings

Maximum Amperage (A)100
Maximum Wattage (W)0
Phase Type1 Phase
Fuse-dependent short-circuit rating10,000 with Class H fuses; 100,000 with Class R fuses. AIC
Grounded B-phase compatibilitySuitable for grounded B-phase system applications.
Short-circuit interrupting rating10,000 with Class H fuses; 100,000 with Class R fuses AIC
Mechanical lug wire rangesLine/load and neutral: #12–1/0 AWG aluminum or #14–1/0 AWG copper; ground: #14–4 AWG.
Conductor temperature ratingFor 60°C or 75°C conductors.
Motor horsepower ratingsAt 240 V AC: 1-phase/3-wire, 7.5 hp standard and 15 hp maximum; 3-phase/3-wire, 15 hp standard and 30 hp maximum. At 250 V DC: 20 hp. Standard ratings use non-time-delay fuses; maximum ratings use time-delay fuses.

Disconnect Configuration

Disconnect TypeSafety Switch
FusedFused
Blade designDouble-break visible blade design.
ServiceabilityModular design allows quick and easy replacement of parts.
Conduit hub provisionProvision for a Type HS hub.
MountingTwo- or three-point mounting with a top keyhole.
Tangential conduit knockout sizesTangential knockout code A: 0.75, 1.00, 1.25, 1.50 in; code B: 1.00, 1.25, 1.50, 2.00 in.
Switching actionQuick-make and break switching action.
Neutral block designThe neutral block is designed to be groundable.
Position indicationHighly visible ON/OFF indication.
Padlocking provisionsPadlockable cover latch and multiple padlock provisions on the handle.
Cover interlockSingle cover interlock.
Door openingSide-opening door opens more than 180°.

Enclosure & Certifications

NEMA Enclosure RatingNEMA 3R
Certifications and ListingsUL Listed
Enclosure thickness0.054 in (17 gauge).
Enclosure finishANSI Grey #61 paint.
Enclosure materialGalvanized steel.
Service-entrance suitabilitySuitable for use as service entrance equipment.
Outdoor exposure protectionProvides a degree of protection against falling rain and sleet and must remain undamaged by ice formation; not intended to protect against dust, internal condensation, or internal icing.
Rain-entry designDouble-overlap enclosure door top helps limit rain entry.

Dimensions & Weight

Height (in.)23.46
Width (in.)11.67
Length (in.)8.7
Weight (lb.)20.6
Wire-bending spaceFused configuration: line side 6.07 in (154 mm); load side 8.10 in (206 mm). in (mm)

Product Documents

Your cart

0 products 0 units

Your cart is empty.