The Siemens HF361NA is a fused, 30 A, three-pole, 600 V heavy-duty indoor safety switch with mechanical lugs. Its listed specifications include fuse-dependent short-circuit and motor ratings, conductor ranges, and service-entrance suitability.
30 A, Three-Pole, 600 V
Fuse-Dependent AIC Ratings
Three-Phase Motor Ratings
Mechanical-Lug Conductor Range
Service-Entrance Suitability
Line-Side Barrier Shields
The Siemens HF361NA is a fused, 30 A, three-pole, 600 V heavy-duty indoor safety switch with mechanical lugs. Its listed specifications include fuse-dependent short-circuit and motor ratings, conductor ranges, and service-entrance suitability.
The Siemens HF361NA is a fused, 30 A, three-pole, 600 V heavy-duty indoor safety switch with mechanical lugs. Its listed specifications include fuse-dependent short-circuit and motor ratings, conductor ranges, and service-entrance suitability.
30 A, Three-Pole, 600 V
Fuse-Dependent AIC Ratings
Three-Phase Motor Ratings
Mechanical-Lug Conductor Range
Service-Entrance Suitability
Line-Side Barrier Shields
Technical Specifications
Product information and specifications for the selected item.
SKU: HF361NA
Product Information
Brand
Siemens
SKU
HF361NA
Category
Disconnects & Safety Switches
Key Specs
Maximum Amperage (A)
30
Maximum Wattage (W)
0
Phase Type
3 Phase
Disconnect Type
Safety Switch
NEMA Enclosure Rating
NEMA 1
Switch Ratings
Maximum Amperage (A)
30
Maximum Wattage (W)
0
Phase Type
3 Phase
Three-phase horsepower rating at 480 V AC
5 hp standard with non-time-delay fuses; 15 hp maximum with time-delay fuses
Short-circuit rating by fuse class
10,000 with Class H fuses; 200,000 with Class R and J fuses AIC
I²t rating
50,000 A²·s
Overload current rating
12Ă—; exceeds the 10Ă— industry standard
Rated supply frequency
50/60 Hz
AIC rating by fuse class
10,000 with Class H fuses; 200,000 with Class R and J fuses AIC
Design E motor compatibility
Horsepower ratings also apply to Design E motors without derating
Three-phase horsepower rating at 600 V AC
7.5 hp standard with non-time-delay fuses; 20 hp maximum with time-delay fuses
600 V DC short-circuit rating
100,000 with Class R or J fuses AIC
Mechanical service life
10,000 (typical) switching cycles
Disconnect Configuration
Disconnect Type
Safety Switch
Fused
Fused
Switching action
Quick-make and break switching action
Lug conversion
Front-removable lugs can be converted to copper-body or compression-type lugs
Line, load and neutral wire range
60/75°C Cu/Al conductors; #12–6 AWG aluminum or #14–6 AWG copper
Electrical connection
Mechanical lugs
Mounting method
Surface fastening; 2-3 point mounting holes
Blade construction
Double-break visible blade design
Cover interlock
Defeatable dual cover interlock
Wire-bending space
Meets NEC wire-bending-space requirements
Position indication
Highly visible ON/OFF indication
Ground wire range
#14–4 AWG
Enclosure & Certifications
NEMA Enclosure Rating
NEMA 1
Certifications and Listings
UL Listed
Line-side barrier protection
Internal shields meet NEC 2020 230.62 line-side barrier requirements