Southwire Romex® SIMpull® Type NM-B cable is 10/3 AWG with three insulated solid-copper conductors and a bare copper ground. Rated 600 V for dry-location work, it has a pink PVC jacket and is sold by the foot.

  • 10/3 Type NM-B Cable
  • Solid Copper Conductors
  • 600 V Rating
  • Pink PVC Jacket
  • Dry-Location Use
  • Cut by the Foot

Product Overview

Southwire Romex® SIMpull® Type NM-B cable is 10/3 AWG with three insulated solid-copper conductors and a bare copper ground. Rated 600 V for dry-location work, it has a pink PVC jacket and is sold by the foot.

Technical Specifications

Product information and specifications for the selected item.

SKU: 10/3 ROMEX 250FT

Product Information

BrandSouthwire
MPN10/3 ROMEX 250FT
SKU10/3 ROMEX 250FT
CategoryNM-B Cable

Key Specs

Wire Gauge10/3
Total Wire Length (ft.)250
Conductor MaterialCopper
Stranded or SolidSolid
Jacket ColorPink

Electrical & Conductor

Wire Gauge10/3
Conductor MaterialCopper
Stranded or SolidSolid
Conductor insulation constructionPVC insulation with a nylon sheath
Voltage rating600 V
Allowable ampacity at 90°C (table value)40 A
Ampacity basisBased on 2023 NEC Table 310.16
Conductor wire specificationASTM B3 — soft or annealed copper wire
Inductive reactance0.05 at 60 Hz; basis is non-ferrous conduit with one-diameter center-to-center spacing. Ω/1000 ft
Phase-conductor insulation color codeBlack, red, and white
DC resistance at 25°C1.04 Ω/1000 ft
Allowable ampacity and application limit30 A at 60°C and 40 A at 90°C per Table 2. Use ampacity is limited to the 60°C-conductor basis; NEC 240.4(D) limits overcurrent protection for 10 AWG copper to 30 A.
Individual conductor insulation temperature rating90°C, for terminations in lighting fixtures
NEC 240.4(D) overcurrent-protection limitation30 A
Allowable ampacity at 60°C30 A
AC resistance at 75°C1.291 Ω/1000 ft

Package & Length

Bundle/SingleSingle Product
Total Wire Length (ft.)250

Jacket & Features

Jacket ColorPink
FeaturesJacketed
UL product standardUL 719 — Nonmetallic-Sheathed Cables
NOM safety standardNOM-063-SCFI — Electrical Products – Conductors – Safety Requirements
Permitted installation locationsSuitable for exposed or concealed work in dry locations; may be run in masonry-block or tile-wall air voids only where the walls are not wet or damp.
Binder materialKraft paper
Federal specificationA-A-59544
Typical applicationPrimarily used in residential wiring as branch circuits for outlets, switches, and other loads.
Individual conductor installation restrictionsIndividual conductors are not listed or marked as THHN or another NEC-recognized conductor type and must not be installed apart from the complete Type NM-B cable. Conductors routed inside panelboards or boxes without the jacket for termination are considered part of the complete cable.
Jacket materialPolyvinyl chloride (PVC)
RoHS specificationRoHS-2 (European Directive 2011/65/EU)
Ground wire wrapKraft paper wrap

Dimensions & Weight

Height (in.)0.63
Minimum bending radius0.9 in