12/2 MC Stranded Cable

0 Reviews
SKU
12-2MC CABLE STRANDED-COIL 250FT

Southwire 12/2 MC Stranded CableAdditional specifications Additional specifications · Compliance Applicable standards Federal Specification A-A59544 (formerly J-C-30B); NFPA 70, Article 330 Environmental compliance RoHS-2 (European Directive 2011/65/EU) Firestop compliance UL 1479 firestop standard; listed for UL 1-, 2-, and 3-hour through-penetrat...

Needs Data

Product Overview

Southwire 12/2 MC Stranded Cable

Additional specifications

Additional specifications · Compliance

Applicable standards Federal Specification A-A59544 (formerly J-C-30B); NFPA 70, Article 330
Environmental compliance RoHS-2 (European Directive 2011/65/EU)
Firestop compliance UL 1479 firestop standard; listed for UL 1-, 2-, and 3-hour through-penetration firestop systems
UL listing and standards UL Listed; UL 83 and UL 1569
Flame testing VW-1 vertical-wire; UL 1685 FT4 and IEEE 1202 FT4 vertical-tray flame tests (70,000 BTU/hr)

Additional specifications · Construction

Insulation construction PVC with nylon sheath; Type THHN/THWN
Conductor colors Black and white
Conductor stranding 19-strand, Class C compressed construction (ASTM B3/B8)
Ground conductor insulation Green PVC with nylon sheath; Type THHN/THWN
Binder tape Mylar or PET tape with a printed legend, wrapped around the assembly

Additional specifications · Electrical

DC resistance at 25°C 1.662 Ω/1000 ft
Inductive reactance at 60 Hz 0.054 Ω/1000 ft
Insulation temperature rating 90°C dry
Rated voltage 600 V
AC resistance at 75°C 2.063 Ω/1000 ft

Additional specifications · Installation

Assembly and theater installation Suitable for Places of Assembly per NEC 518.4 and theaters per NEC 520.5
Raised-floor IT installation Suitable under raised floors for information technology equipment conductors and cables per NEC Article 645
Anti-short bushing requirement Not required
Hazardous-location suitability Class I Division 2, Class II Division 2, and Class III Division 1
Air-handling space installation Suitable for environmental air-handling spaces per NEC 300.22(C)
Cable tray and raceway compatibility Suitable for installation in cable tray and approved raceways
Minimum bend radius 3.5 in
Installation methods Fished or embedded in plaster; suitable for concealed or exposed installations

Additional specifications · Applications

Power distribution application Suitable for branch and service power distribution in commercial, industrial, institutional, and multi-residential buildings

Technical Specifications

Product information and specifications for the selected item.

SKU: 12-2MC CABLE STRANDED-COIL 250FT

Product Information

BrandSouthwire
MPN12-2MC CABLE STRANDED-COIL 250FT
SKU12-2MC CABLE STRANDED-COIL 250FT
CategoryMC Cable & Armored Cable

Key Specs

Wire Gauge12/2
Maximum Amperage (A)30
Conductor MaterialCopper
Indoor/OutdoorIndoor

Electrical & Conductor

Wire Gauge12/2
Maximum Amperage (A)30
Conductor MaterialCopper
Insulation constructionPVC with nylon sheath; Type THHN/THWN
DC resistance at 25°C1.662 Ω/1000 ft
Conductor colorsBlack and white
Inductive reactance at 60 Hz0.054 Ω/1000 ft
Conductor stranding19-strand, Class C compressed construction (ASTM B3/B8)
Ground conductor insulationGreen PVC with nylon sheath; Type THHN/THWN
Insulation temperature rating90°C dry
Rated voltage600 V
Binder tapeMylar or PET tape with a printed legend, wrapped around the assembly
AC resistance at 75°C2.063 Ω/1000 ft

Ratings & Features

Indoor/OutdoorIndoor
FeaturesHeat Resistant
Applicable standardsFederal Specification A-A59544 (formerly J-C-30B); NFPA 70, Article 330
Environmental complianceRoHS-2 (European Directive 2011/65/EU)
Assembly and theater installationSuitable for Places of Assembly per NEC 518.4 and theaters per NEC 520.5
Raised-floor IT installationSuitable under raised floors for information technology equipment conductors and cables per NEC Article 645
Firestop complianceUL 1479 firestop standard; listed for UL 1-, 2-, and 3-hour through-penetration firestop systems
Power distribution applicationSuitable for branch and service power distribution in commercial, industrial, institutional, and multi-residential buildings
Anti-short bushing requirementNot required
Hazardous-location suitabilityClass I Division 2, Class II Division 2, and Class III Division 1
UL listing and standardsUL Listed; UL 83 and UL 1569
Air-handling space installationSuitable for environmental air-handling spaces per NEC 300.22(C)
Cable tray and raceway compatibilitySuitable for installation in cable tray and approved raceways
Minimum bend radius3.5 in
Flame testingVW-1 vertical-wire; UL 1685 FT4 and IEEE 1202 FT4 vertical-tray flame tests (70,000 BTU/hr)
Installation methodsFished or embedded in plaster; suitable for concealed or exposed installations

Dimensions & Weight

Height (in.)0.496