Square D 3-Terminal QO/Homeline Load Center Ground Bar Kit
0 Reviews
SKU
PK3GTA1
Square D by Schneider Electric’s PK3GTA1 is a field-installable, three-terminal ground bar kit for QO and Homeline load centers, specified as the standard ground bar for 2-space load centers. It mounts directly to the back of the enclosure and accepts the listed copper and aluminum conductor combinations.
QO and Homeline Compatibility
Three Terminals
Copper and Aluminum Capacity
Standard for 2-Space Load Centers
Direct Enclosure Mounting
Binding Screw Torque
Square D by Schneider Electric’s PK3GTA1 is a field-installable, three-terminal ground bar kit for QO and Homeline load centers, specified as the standard ground bar for 2-space load centers. It mounts directly to the back of the enclosure and accepts the listed copper and aluminum conductor combinations.
Square D by Schneider Electric’s PK3GTA1 is a field-installable, three-terminal ground bar kit for QO and Homeline load centers, specified as the standard ground bar for 2-space load centers. It mounts directly to the back of the enclosure and accepts the listed copper and aluminum conductor combinations.
QO and Homeline Compatibility
Three Terminals
Copper and Aluminum Capacity
Standard for 2-Space Load Centers
Direct Enclosure Mounting
Binding Screw Torque
Technical Specifications
Product information and specifications for the selected item.
SKU: PK3GTA1
Product Information
Brand
Square D by Schneider Electric
MPN
PK3GTA1
SKU
PK3GTA1
UPC / GTIN
785901156932
Category
Ground Bars & Busbars
Key Specs
Length (in.)
0.312
Width (in.)
1.4
Capacity & Compliance
Dual-conductor combinations
Two No. 14 or No. 12 copper conductors, or two No. 12 or No. 10 aluminium conductors AWG
EU RoHS status
Compliant without the use of exemption (10 substances)
Installation type
Field-installable.
Mounting screw torque
30 (3.4 N·m), after overcoming starting torque lb-in
Conductor capacity per terminal
Copper: one #14–#4 AWG conductor or two #14 or #12 AWG conductors; aluminum: one #12–#4 AWG conductor or two #12 or #10 AWG conductors.
REACH SVHC status
No SVHC above the 0.1% threshold at part level
Compatible load-center lines
QO and Homeline load centers.
Standard load-center application
Standard ground bar for 2-space load centers.
REACH Annex XVII status
No substance restricted under REACH Annex XVII is used within the scope of restriction
Binding-screw torque (single conductor)
#4 and #6 Cu/Al: 35 lb-in; #8 Cu/Al: 25 lb-in; #10–#14 Cu and #10–#12 Al: 20 lb-in.
Conductor size range
14–4 copper; 12–4 aluminium AWG
Load-center series
QO and Homeline
Mounting method
Direct mounting to the back of the enclosure
Dimensions & Weight
Height (in.)
0.437
Width (in.)
1.4
Length (in.)
0.312
Weight (lb.)
0.0441
Mounting-hole preparation
If mounting provisions are absent, drill one 0.147 in diameter hole using the bar as a drilling template
Product Documents
UL Certificate of Compliance — 20140510-E6294
Certification compliance
Open / download file