Square D by Schneider Electric, Class 8910 DPA23 Definite-Purpose Contactor, 25A, 3P, 24VAC Coil
0 Reviews
SKU
DPA23
The Square D by Schneider Electric Class 8910 DPA23 is an open-style, three-pole definite-purpose contactor rated 25 A, with normally open contacts and a 24 VAC, 50/60 Hz coil. Its motor ratings reach 20 hp at 575 VAC, three-phase, and its maximum voltage rating is 600 VAC.
25 A, 3-pole contactor
24 VAC, 50/60 Hz coil
Normally open contacts
Motor ratings up to 20 hp
600 VAC maximum voltage
35 A resistive-load rating
The Square D by Schneider Electric Class 8910 DPA23 is an open-style, three-pole definite-purpose contactor rated 25 A, with normally open contacts and a 24 VAC, 50/60 Hz coil. Its motor ratings reach 20 hp at 575 VAC, three-phase, and its maximum voltage rating is 600 VAC.
The Square D by Schneider Electric Class 8910 DPA23 is an open-style, three-pole definite-purpose contactor rated 25 A, with normally open contacts and a 24 VAC, 50/60 Hz coil. Its motor ratings reach 20 hp at 575 VAC, three-phase, and its maximum voltage rating is 600 VAC.
25 A, 3-pole contactor
24 VAC, 50/60 Hz coil
Normally open contacts
Motor ratings up to 20 hp
600 VAC maximum voltage
35 A resistive-load rating
Technical Specifications
Product information and specifications for the selected item.
SKU: DPA23
Product Information
Brand
Square D by Schneider Electric
MPN
DPA23
SKU
DPA23
Category
Lighting Contactors
Key Specs
Number of Poles
3
Coil Voltage
24 VAC
Contact Type
N.O.
Height (in.)
4
Switching & Electrical
Number of Poles
3
Coil Voltage
24 VAC
Contact Type
N.O.
Terminal torque
22 for 20–30 FLA lb-in
Switching requirement above 240 V
All lines must be switched above 240 V
Rated operational voltage
600 V AC
Coil apparent-power burden
60 inrush; 6 sealed VA
Product certifications
CE, CSA, UL listed
California Proposition 65 warning
Cancer and Reproductive Harm
RoHS status
Will not be Compliant
Duty cycle
Continuous
Electrical life
200,000 operations
Operating temperature
0–65 °C (32–149 °F)
Control-circuit frequency
50/60 Hz
REACh statement
Reference not containing SVHC above the threshold
Coil replaceability
Coils are not replaceable
Maximum component SCCR, breaker-protected
100 kA at 480 V with a circuit breaker up to 80 A
Horsepower ratings by voltage and phase
2 at 115 VAC 1-phase; 5 at 230 VAC 1-phase; 10 at 230 VAC 3-phase; 15 at 460 VAC and 20 at 575 VAC 3-phase HP
Locked-rotor rated current
150 at 277 V AC; 125 at 460 V AC; 100 at 575 V AC
Power-terminal conductor material
Solid or stranded copper wire only
Maximum voltage rating
600 VAC
Mechanical life
500,000 operations
Motor horsepower ratings
2 at 115 V AC, 1 phase; 5 at 230 V AC, 1 phase; 10 at 230 V AC, 3 phases; 15 at 460 V AC, 3 phases; 20 at 575 V AC, 3 phases hp