The Square D PK9GTA is a nine-terminal equipment grounding bar kit for QO/Homeline load centers and 12-circuit NQOD panelboard applications up to 225 A. The kit includes a tin-plated aluminum bar, two mounting screws, and an equipment-grounding label.

  • Nine grounding terminals
  • QO/Homeline load-center compatibility
  • NQOD panelboard application
  • Tin-plated aluminum bar
  • Listed conductor combinations
  • CSA certified

The Square D PK9GTA is a nine-terminal equipment grounding bar kit for QO/Homeline load centers and 12-circuit NQOD panelboard applications up to 225 A. The kit includes a tin-plated aluminum bar, two mounting screws, and an equipment-grounding label.

Product Overview

The Square D PK9GTA is a nine-terminal equipment grounding bar kit for QO/Homeline load centers and 12-circuit NQOD panelboard applications up to 225 A. The kit includes a tin-plated aluminum bar, two mounting screws, and an equipment-grounding label.

  • Nine grounding terminals
  • QO/Homeline load-center compatibility
  • NQOD panelboard application
  • Tin-plated aluminum bar
  • Listed conductor combinations
  • CSA certified

Technical Specifications

Product information and specifications for the selected item.

SKU: PK9GTA

Product Information

BrandSquare D
MPNPK9GTA
SKUPK9GTA
UPC / GTIN785901026396
CategoryGround Bars & Busbars

Key Specs

Certifications and ListingsCSA Certified
Length (in.)0.312
Width (in.)3.8

Capacity & Compliance

Certifications and ListingsCSA Certified
Terminal torque for one #8 Cu/Al conductor25 lb-in
Supported conductor sizes14 AWG...10 AWG copper; 12 AWG...10 AWG aluminium; 8 AWG aluminium/copper; 6 AWG...4 AWG aluminium/copper; 14 AWG...12 AWG
Maximum conductors per terminal3 wires per terminal
Panelboard familyNQ
Load-center familyQO/Homeline
Power isolation before installationTurn off all power before working on or inside the equipment; use a properly rated voltage-sensing device to confirm power is off.
Installer qualificationInstallation and service by qualified electrical personnel only
QO/Homeline load-center compatibilitySquare D QO/Homeline convertible-main load centers, 100–225
Supported conductor constructionSolid or stranded
Permitted conductor sizes and counts1 × #14–#4 AWG Cu/Al; 2 or 3 × #14 AWG Cu; 2 or 3 × #12 AWG Cu/Al; 2 or 3 × #10 AWG Cu/Al
Terminal torque for listed multiple-wire terminations25 for 2–3 × #14 Cu, 2–3 × #12 Cu/Al, or 2–3 × #10 Al lb-in
Terminal torque for one #10–#14 Cu or #10–#12 Al conductor20 lb-in
Terminal torque for one #4 or #6 Cu/Al conductor35 lb-in
NQOD panelboard application limit225 A
Maximum amperage stated for NQ panelboard application225 A
Terminal tightening torque20 for 14 AWG...10 AWG copper; 20 for 12 AWG...10 AWG aluminium; 35 for 6 AWG...4 AWG lb.in

Dimensions & Weight

Height (in.)0.437
Width (in.)3.8
Length (in.)0.312
Weight (lb.)0.085
Mounting-hole preparationIf mounting holes are absent, drill two 0.147 in (3.7 mm) diameter holes with a #26 drill, using the bar as a template; keep metal shavings out of the enclosure interior.
Included kit components1 equipment grounding bar, 2 mounting screws, 1 equipment grounding label
Included installation hardware and labelTwo mounting screws and one equipment-grounding label
Mounting locationMounts to the back of the enclosure
Mounting-screw tightening torque30 after overcoming starting torque lb-in (N•m)
Mounting methodDirect mounting back of enclosure
Ground bar material and finishTin-plated aluminum
Grounding-label placementApply the equipment grounding bar label to the enclosure beside the bar.

Product Documents