Skip to content

Square D QO 20A 2-Pole GFCI Circuit Breaker, 120/240VAC

0 Reviews
SKU
QO220GFI

The Square D QO220GFI is a 20 A, two-pole miniature GFCI circuit breaker for 120/240 V AC. It provides Class A ground-fault protection at 6 mA, has a 10 kA interrupting capacity, and uses plug-on mounting with a pigtail neutral lead.

  • 20 A, Two-Pole Rating
  • Class A 6 mA GFCI
  • 10 kA Interrupting Capacity
  • QO Panel Compatibility
  • Plug-On Mounting
  • Pigtail Neutral Lead

Product Overview

The Square D QO220GFI is a 20 A, two-pole miniature GFCI circuit breaker for 120/240 V AC. It provides Class A ground-fault protection at 6 mA, has a 10 kA interrupting capacity, and uses plug-on mounting with a pigtail neutral lead.

Technical Specifications

Product information and specifications for the selected item.

SKU: QO220GFI

Product Information

BrandSquare D
MPNQO220GFI
SKUQO220GFI
UPC / GTIN785901562993
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)20
Voltage120/240 V AC
Interruption TypeGFCI
Breaker TypeMiniature
Mounting TypePlug-On
Neutral Connection TypePigtail

Electrical Ratings

Maximum Amperage (A)20
Voltage120/240 V AC
Interruption TypeGFCI
Conductor size rangeCopper: 14–8; aluminium: 12–8 AWG
Overload and short-circuit protectionProtects against overloads and short-circuits.
Conductor temperature compatibilitySuitable for conductor insulation rated 60 or 75 °C
Load-conductor run guidance250 (76) maximum total one-way load-conductor run to minimize nuisance tripping. ft (m)
Test frequencyTest after installation and monthly thereafter.
Ambient operating rating40 °C
Ambient rating104 °F (40 °C)
Electrical testing restrictionMegger, high-voltage, and hi-pot tests can damage the GFCI; isolate it before such tests.

Breaker Configuration

Breaker TypeMiniature
Mounting TypePlug-On
Neutral Connection TypePigtail
Series TypeQO
Line-side wiring requirementSwitch both ungrounded (hot) conductors; connect the incoming line to the load-center bus.
Supply system requirementUse only with grounded-neutral electrical systems.
Terminal connection stylePressure plate
Panel compatibility / space requirementCompatible with QO electrical panels and CSEDs; requires 2 spaces.
Compatible panel systemsQO load centers; NQ and NQOD panelboards; OEM mounting bases; Speed-D switchboard distribution panels
Load-neutral conductor requirementOptional for 2-pole QO-GFI breakers in the 15–50 A range
Panel neutral wiring requirementConnect the panel neutral wire to the load-center or panelboard neutral bar for correct GFCI operation.
Panel spaces required2 spaces
Terminal conductor countSingle-wire terminations for QO-GFI 15–30 A models
Tightening torque35.4 lbf.in (4 N.m) and 40.7 lbf.in (4.6 N.m)
Pigtail lead length18 (457) in (mm)
Load-terminal connectionPressure plate

Pack & Smart Features

Bundle/SingleSingle Product
Pack OptionsSingle Item
Trip indicationA Visi-Trip indicator helps identify tripped breakers.

Certifications

Certifications and ListingsCSA Certified, ROHS, UL Listed
EU RoHS statusCompliant with exemptions 7(a), 7(c)-I
REACH SVHC statusSVHC are declared above the 0.1% threshold at part level.
REACH Annex XVII restriction statusNo substance under REACH Annex XVII is used within the scope of restriction.

Dimensions & Weight

Height (in.)4.1
Width (in.)1.5
Length (in.)2.9

Product Documents