Skip to content

Square D QO 30A 1P 120VAC Class A GFCI Circuit Breaker

0 Reviews
SKU
QO130GFI

The Square D QO130GFI is a 30 A, single-pole, 120 V AC miniature circuit breaker with Class A GFCI protection and a 6 mA trip threshold. It provides overload and short-circuit protection with QO-series plug-in mounting and a pigtail neutral.

  • 30 A, single-pole, 120 V AC
  • Class A GFCI, 6 mA trip
  • Overload and short-circuit protection
  • QO-series plug-in mounting
  • 18 in neutral pigtail
  • Pressure-plate, single-wire terminals

The Square D QO130GFI is a 30 A, single-pole, 120 V AC miniature circuit breaker with Class A GFCI protection and a 6 mA trip threshold. It provides overload and short-circuit protection with QO-series plug-in mounting and a pigtail neutral.

Product Overview

The Square D QO130GFI is a 30 A, single-pole, 120 V AC miniature circuit breaker with Class A GFCI protection and a 6 mA trip threshold. It provides overload and short-circuit protection with QO-series plug-in mounting and a pigtail neutral.

  • 30 A, single-pole, 120 V AC
  • Class A GFCI, 6 mA trip
  • Overload and short-circuit protection
  • QO-series plug-in mounting
  • 18 in neutral pigtail
  • Pressure-plate, single-wire terminals

Technical Specifications

Product information and specifications for the selected item.

SKU: QO130GFI

Product Information

BrandSquare D
MPNQO130GFI
SKUQO130GFI
UPC / GTIN785901255093
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)30
Voltage120 V AC
Interruption TypeGFCI
Breaker TypeMiniature
Mounting TypePlug-On
Neutral Connection TypePigtail

Electrical Ratings

Maximum Amperage (A)30
Voltage120 V AC
Interruption TypeGFCI
GFCI test intervalTest after installation and monthly thereafter
Conductor temperature ratingSuitable for 60°C or 75°C conductors
Permitted conductor sizesCopper: AWG 14–8; aluminum: AWG 12–8
Maximum one-way load-conductor run250 ft
Tightening torque35.4 lbf.in (4 N.m); 40.7 lbf.in (4.6 N.m)
High-voltage test restrictionDo not megger or hi-pot test; voltage above 240 Vac can damage the GFCI electronics.
Trip indicationThe Visi-Trip indicator shows a trip, and the operating handle moves to the center tripped position.
Ground-fault test functionThe test button trips the GFCI and shows a trip indication when the pigtail is correctly connected to the panel neutral assembly.
Ambient rating104 °F (40 °C)
Conductor wire sizes14–8 copper; 12–8 aluminium AWG

Breaker Configuration

Breaker TypeMiniature
Mounting TypePlug-On
Neutral Connection TypePigtail
Series TypeQO
Electrical terminal connectionPressure plate
Pigtail lead length18 in (457 mm)
Main-breaker and backfeed restrictionNot for use as a panelboard main breaker or in reverse-connected (backfed) applications.
Panel spaces required1 space
Supply-system requirementMust be supplied by a grounded-neutral electrical system
Terminal configurationPressure-plate terminals support single-wire terminations.
Circuit configurationRequires an independent circuit; a neutral shared with more than one panel circuit conductor cannot provide ground-fault protection.

Pack & Smart Features

Bundle/SingleSingle Product
Pack OptionsSingle Item

Certifications

Certifications and ListingsCSA Certified, ROHS, UL Listed
Mercury-freeYes
Total lifecycle carbon footprint38 kg CO2 eq.

Dimensions & Weight

Height (in.)4.13
Width (in.)0.75
Length (in.)2.91
Weight (lb.)0.269

Product Documents

Your cart

0 products 0 units

Your cart is empty.

Add products as you browse, then review them here.