The Square D QO240GFI is a 40 A, two-pole plug-in GFCI circuit breaker in the QO series for 120/240 V AC. It provides Class A 6 mA ground-fault protection, has a 10 kA interrupt rating and an 18 in (457 mm) pigtail neutral lead, and can operate with or without a load-neutral wire.
40 A Two-Pole Breaker
Class A 6 mA GFCI
10 kA Interrupt Rating
QO Plug-In Format
18 in Pigtail Neutral Lead
Copper and Aluminum Conductor Ranges
The Square D QO240GFI is a 40 A, two-pole plug-in GFCI circuit breaker in the QO series for 120/240 V AC. It provides Class A 6 mA ground-fault protection, has a 10 kA interrupt rating and an 18 in (457 mm) pigtail neutral lead, and can operate with or without a load-neutral wire.
The Square D QO240GFI is a 40 A, two-pole plug-in GFCI circuit breaker in the QO series for 120/240 V AC. It provides Class A 6 mA ground-fault protection, has a 10 kA interrupt rating and an 18 in (457 mm) pigtail neutral lead, and can operate with or without a load-neutral wire.
40 A Two-Pole Breaker
Class A 6 mA GFCI
10 kA Interrupt Rating
QO Plug-In Format
18 in Pigtail Neutral Lead
Copper and Aluminum Conductor Ranges
Technical Specifications
Product information and specifications for the selected item.
SKU: QO240GFI
Product Information
Brand
Square D
MPN
QO240GFI
SKU
QO240GFI
UPC / GTIN
785901764854
Category
Circuit Breakers
Key Specs
Maximum Amperage (A)
40
Voltage
120/240 V AC
Interruption Type
GFCI
Breaker Type
Miniature
Mounting Type
Plug-On
Neutral Connection Type
Pigtail
Electrical Ratings
Maximum Amperage (A)
40
Voltage
120/240 V AC
Interruption Type
GFCI
Copper conductor range
14–6 AWG
Conductor size range
12–4 AWG aluminum; 14–6 AWG copper
Ambient rating
104 °F (40 °C) °F; °C
Aluminum conductor range
12–4 AWG
Maximum one-way load-conductor run
250 ft (76 m) total one-way load-conductor run ft; m
Terminal tightening torque
44.3 lbf.in (5 N.m); 40.7 lbf.in (4.6 N.m), with the latter specified for 12–4 AWG / 4–20 mm²
Compatible conductor temperature rating
75 °C
Breaker Configuration
Breaker Type
Miniature
Mounting Type
Plug-On
Neutral Connection Type
Pigtail
Series Type
QO
Load-neutral wiring compatibility
Can operate with or without a load-neutral wire.
Supply-system requirement
Grounded-neutral electrical systems only
Panel spaces required
2 spaces
Pigtail lead length
18 in (457 mm) in; mm
Multipole trip behavior
An overcurrent on any pole opens all poles simultaneously.
GFCI line-wiring requirement
Switch both ungrounded (hot) conductors; connect incoming line to the load-center bus
Panel-neutral wiring
Connect panel neutral to the load-center or panelboard neutral bar for GFCI operation
Electrical terminal connection
Pressure plate
Pack & Smart Features
Bundle/Single
Single Product
Pack Options
Single Item
Trip indicator
Visi-Trip visual indication when tripped
Test-equipment limitation
Megger, high-voltage, or hi-pot tests can damage the GFCI
Certifications
Certifications and Listings
CSA Certified, ROHS, UL Listed
Mercury content
Mercury-free
REACH Annex XVII status
No Annex XVII substance is used within the scope of restriction
EU RoHS status
Compliant with exemptions 7(a), 7(c)-I
REACH SVHC disclosure
SVHC present above the 0.1% threshold at part level